Inspections for the day of: Tuesday, May 5, 2020.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00676 Final5/5/20205/5/20205/6/2020 8:31:49 AMPPASS
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE19-00601 Electrical Rough-In5/5/20205/5/20205/6/2020 8:24:52 AMPPASS
4th Floor rough in. Danny is contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Units 402 thru 424 bathrooms, and hvac, and vending walls and hardlids rough in ok cover
ELE20-01518 Electrical Rough-In5/5/20205/5/20205/5/2020 1:41:43 PMPFAIL
Rough in inspection at new Roosevelt Market Phone #: ###-#### Inspection requested via web by Steve Craig
300.22(B)- MC cable shall not be installed in air handling spaces.
314.20- MC cables shall terminate in a box.
330.30- MC cables shall be secured by approved means with in 12" of a box.
City approved set of prints on site
ELE20-01496 Rough-In Permanent Service5/4/20205/5/20205/5/2020 12:02:08 PMAFAIL
Phone #: ###-#### Inspection requested via web by Troy Ballard
110.3- Meter base can not listed to receive a 3" underground conduit. Unable to install meter cover due to conduit coupling.
300.4- Nail plates needed in laundry rm, rt of furnace kit side, left kit counter, nook under window, m. bed corner, spare bed, hall closet.
314.25- recessed con cover shall completely enclose box in family room.
ELE20-00440 Final5/5/20205/5/20205/5/2020 11:20:23 AMAPASS
Will need to make sure we have badge access to the basement to look at generator location. Phone #: ###-#### Inspection requested via web by Jim Noll Final ok
ELE20-00440 Electrical Rough-In5/5/20205/5/20205/5/2020 10:57:46 AMPPASS
Will need to make sure we have badge access to the basement to look at generator location. Phone #: ###-#### Inspection requested via web by Jim Noll
Removed existing generator and ATS and installed new ones. Common neutral block no GEC required. Rough in ok
ELE20-01069 Electrical Rough-In5/4/20205/5/20205/5/2020 10:55:56 AMAPART
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Except south corridor around restrooms, rest of grid rough in ok cover.
ELE20-01102 Electrical Rough-In5/4/20205/5/20205/5/2020 9:53:34 AMAFAIL
Underground rough-in please. Have a bless week! Phone #: ###-#### Inspection requested via web by Kyle Lott
Unable to inspect due to portion of job needing inspection is part of a plan mod still under review. Recall when plan mod complete and city approved set of prints in on site.
ELE20-01105 Electrical Rough-In5/4/20205/5/20205/5/2020 9:12:45 AMAPASS
6 Light pole bases and ug piping to bases Phone #: ###-#### Inspection requested via web by John Rourke
6 pole bases on west side of upper lot and underground 2 central runs east and west to lower central pole bases rough in ok cover