Inspections for the day of: Tuesday, May 5, 2020.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00266 INSP-Final Inspection5/4/20205/5/20205/5/2020 1:37:28 PMPFAIL
No devices tested, horn strobes and pull stations from old fire alarm system are still in place, non-functioning fire alarm devices must be removed before final inspection can be completed, per installing contractor old devices in place are not integrated with the new fire alarm panel, also old devices are not compliant with the current NFPA72.

Please call 1/2hour prior Phone #: ###-#### Inspection requested via web by Rick Groom
FIR20-00165 INSP-Final Inspection5/5/20205/5/20205/5/2020 1:34:22 PMPCANC
Cancelled per conversation with point of contact, inspection request will be rescheduled for a later date.

RICK FRY IS OUR CONTACT. G.C. WANTS TO DO THIS AT THE SAME TIME AS THE ALARM CONTRACTOR IS DOING HIS THIS AFTERNOON. Phone #: ###-#### Inspection requested via web by Brad Bettencourt
BLD18-03383 FIRE-Final Inspection5/4/20205/5/20205/5/2020 9:44:07 AMAFAIL
Provide exit/e,emergency light that was shown in the basement that is noted on the city approved drawings as not placed. Provide egress light in basement that is noted on the city approved drawings as not placed. Provide signage for the fire sprinkler riser room and fire alarm control panel (FACP is acceptable). Provide code compliant door hardware on two storage rooms, basement level, rooms noted on city approved drawings have round type door hardware.

Jon Phone #: ###-####
FIR20-00271 INSP-Sprinkler Rough-in5/5/20205/5/20205/5/2020 8:27:07 AMAPART
Rough to cover inspection for hardlids in area of work complete, hardlids approved for cover.

Jon Olmstead Phone #: ###-#### Inspection requested via web by Brodie Stenquist