Inspections for the day of: Tuesday, May 6, 1997.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJoe Tawney
TitleFIRE INSPECTOR
Phone #340-1295
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD96-00464 INSP - Final4/30/19975/6/19975/6/1997 12:00:00 AMAFAIL
BILL HART ###-####. WANTS 10 A.M. FINAL INSP FAIL DP SYSTEM DID NOT MAKE TIME DOOR HDWRE & SMOKE SEALS NOT INSTALLED ALARMS IN HANDICAP ROOMS SPKLR PROTECTION IN STAIRWELLS LOCATION OF STROBES IN CORRIDORS PAINT & STRIPE CURBS ROTATE FIRE HYD
BLD96-01205 INSP - Final4/30/19975/6/19975/6/1997 12:00:00 AMAFAIL
HE WOULD LIKE THIS AT 10 A.M. A MAN FROM HEALTH DEPT.WANTS TO MEET THERE AT THIS TIME. BILL HART ###-####. FINAL INSP FAIL DP SYSTEM DID NOT MEET TIME DOOR HDWRE & SMOKE SEALS NOT INSTALLED SPKLR PROTECTION NEEDED IN STAIR WELLS ALARMS IN HANDICAP ROOMS STROBES NOT PROP PLACED IN CORRIDORS PAINT & STRIPE CURBS ROTATE HYDRANT
BLD96-02918 INSP-Final Inspection5/5/19975/6/19975/6/1997 12:00:00 AMAPASS
REINSP FOR FINAL OK FOR PERM OCC
BLD95-01438 INSP-Sprinkler Rough-in/Hydro5/5/19975/6/19975/6/1997 12:00:00 AMPPART
OK ON HYDRO TEST FOR WP AND DP SYSTEMS ALSO AIR TEST ON DP SYSTEM