ELE02-00740
| Final | 5/3/2002 | 5/6/2002 | 5/6/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 05/03/2002 at 14:50:06. Contact: ###-####. cor. posted called 220 calc p/s, 200.6 #6 or smaller shall not ID, 406.8 bubble cover, 680.26 needs #8 solid for bonding, 680.22 outlets for pool and spa 10ft to 20ft,680.25 needs insulated equip grd from spa switch too spa, 314.23 secure pool light box, 300.12 use connector too terminate non metallic seal tight to spa cabinet, 110.14 use sta-cons for stranded wire terminations 5/6/2002 2:01:56 PM
|
ELE01-03113
| Electrical Rough-In | 5/6/2002 | 5/6/2002 | 5/6/2002 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 05/06/2002 at 07:14:25. Contact: ###-####. rm 139 office 5/6/2002 11:42:18 AM
|
ELE02-00674
| Final | 5/6/2002 | 5/6/2002 | 5/6/2002 12:00:00 AM | P | CANC |
|
|
###-#### not ready 5/6/2002 1:48:34 PM
|
ELE02-00203
| Electrical Rough-In | 5/6/2002 | 5/6/2002 | 5/6/2002 12:00:00 AM | P | PART |
|
|
MOUNTING OF EXTERIOR LIGHT FIXTURES (###-####)RANDY store wide r/i ok need outlets on for hvac within 25 ft of units 210.63, note the way they will feed fixtures with cable ok no boxes are required 5/6/2002 6:02:17 PM
|
ELE02-01338
| Electrical Rough-In | 5/6/2002 | 5/6/2002 | 5/6/2002 12:00:00 AM | P | CANC |
|
|
FOR CONF- KEVIN ###-#### contractor called to cancel inspection 5/6/2002 3:25:20 PM
|
ELE02-01170
| Electrical Rough-In | 5/6/2002 | 5/6/2002 | 5/6/2002 12:00:00 AM | P | FAIL |
|
|
INTERIOR WALL INSPECT ###-#### WARREN cor. posted called 110.14(A) stranded wire under grd screws not allowed, 314.20 mud rings shall be flush with combustible material 5/6/2002 4:59:08 PM
|
ELE01-04190
| Final | 5/6/2002 | 5/6/2002 | 5/6/2002 12:00:00 AM | P | PASS |
|
|
WARREN ###-#### ok 5/6/2002 1:48:03 PM
|
ELE02-00625
| Final | 5/6/2002 | 5/6/2002 | 5/6/2002 12:00:00 AM | P | NR |
|
|
###-#### JUSTIN will call when ready 5/6/2002 3:17:55 PM
|