Inspections for the day of: Monday, May 6, 2002.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00131 INSP-Sprinkler Rough-in/Hydro5/3/20025/6/20025/6/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 05/03/2002 at 10:12:58. Contact: ###-####. head not installed in closet; attic heads not installed; straps needed throughout 5/6/2002 11:29:24 AM
BLD01-00653 FIRE-Final Inspection5/3/20025/6/20025/6/2002 12:00:00 AMACANC
FIRE FN- FRANK- ###-#### completed on 5/3/02 5/6/2002 8:32:13 AM
BLD02-00570 FIRE-Final Inspection5/6/20025/6/20025/6/2002 12:00:00 AMPFAIL
fire fn insp- harold ###-#### rated doors not installed; see BLD01-02970 for shell requirements; told GC to go through Dave Miller for temp occ requirements 5/6/2002 3:44:48 PM
BLD01-02970 FIRE-Final Inspection5/6/20025/6/20025/6/2002 12:00:00 AMPFAIL
harold ###-#### fire fn exit signs; rated doors not installed; handrails not installed; address; detectors for AHU shutdown; elevator not complete/inspected nor alarm panel for recall; 5/6/2002 3:43:42 PM