BLD01-02557
| FIRE-Final Inspection | 5/5/2003 | 5/6/2003 | 5/6/2003 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 5/6/2003 11:19:38 AM
|
FIR03-00128
| INSP-Sprinkler Rough-in | 5/6/2003 | 5/6/2003 | 5/6/2003 12:00:00 AM | P | FAIL |
|
|
The sprinkler piping and risers as installed do not match the approved plans. Resubmit plans that show as-built information. Do not cover pipe until plans have been approved and reinspected. A do not cover sticker was left at project. The east side second floor apartment plan shows 1 1/2 pipe to be installed. 1" is installed. Could not verify piping per notes #5, #6 and #7. Per review note #8 1 1/2 pipe is to be installed but 1 1/4 is installed. Resubmitt calculations. No other items inspected 5/6/2003 2:59:50 PM
|
FIR03-00185
| INSP-Sprinkler Rough-in | 5/6/2003 | 5/6/2003 | 5/6/2003 12:00:00 AM | P | PASS |
|
|
RICK; Phone #: ###-#### Fire sprinkler roughin ok. Sprinklers are ok to cover. Hole in wall needs patched 5/6/2003 11:44:27 AM
|
FIR03-00055
| INSP-Alarm Testing | 5/2/2003 | 5/6/2003 | 5/6/2003 12:00:00 AM | P | NR |
|
|
Troy Peterson, the technitician for AEI wanted to test all devices before my inspection. It wasn't done prior. I agreed. 5/6/2003 2:44:39 PM
|
FIR03-00127
| INSP-Alarm Testing | 5/2/2003 | 5/6/2003 | 5/6/2003 12:00:00 AM | P | FAIL |
|
|
Smoke detector is not compatible with the fire alarm panel. No inspection done 5/6/2003 2:48:59 PM
|
FIR03-00030
| INSP-Final Inspection | 5/5/2003 | 5/6/2003 | 5/6/2003 12:00:00 AM | P | FAIL |
|
|
No approved plans on site. To be rescheduled for tomorrow 5/6/2003 1:38:05 PM
|
FIR03-00078
| INSP-Sprinkler Rough-in/Hydro | 5/5/2003 | 5/6/2003 | 5/6/2003 12:00:00 AM | P | PASS |
|
|
Jonathon is Foreman on site. Later afternoon inspection around 3:00 if possible.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
|