Inspections for the day of: Friday, May 6, 2005.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00061 INSP-Final Inspection5/5/20055/6/20055/6/2005 2:57:40 PMPFAIL
Fail inspection, provide correct cd rating on strobes in reception area as per. plan indicates. Provide smoke alarm address correction to match floor plan of restrooms (men's and women's). Provide pull station that matches type on submittals at address
FIR04-00730 INSP-Final Inspection5/5/20055/6/20055/6/2005 10:22:10 AMAFAIL
Fail inspection, tamper switch on OS&Y in pit activated waterflow alarm. Two PIV tamper switches need adjustment. Control valve tamper switch is incorrectly addressed as attic waterflow. Need to test remaining sprinkler alarms. Heat and smoke detector
BLD04-01700 FIRE-Final Inspection5/6/20055/6/20055/6/2005 12:00:00 AMPPASS
Fire life safety finaled.