FIR05-00061
| INSP-Final Inspection | 5/5/2005 | 5/6/2005 | 5/6/2005 2:57:40 PM | P | FAIL |
|
|
Fail inspection, provide correct cd rating on strobes in reception area as per. plan indicates. Provide smoke alarm address correction to match floor plan of restrooms (men's and women's). Provide pull station that matches type on submittals at address
|
FIR04-00730
| INSP-Final Inspection | 5/5/2005 | 5/6/2005 | 5/6/2005 10:22:10 AM | A | FAIL |
|
|
Fail inspection, tamper switch on OS&Y in pit activated waterflow alarm. Two PIV tamper switches need adjustment. Control valve tamper switch is incorrectly addressed as attic waterflow. Need to test remaining sprinkler alarms. Heat and smoke detector
|
BLD04-01700
| FIRE-Final Inspection | 5/6/2005 | 5/6/2005 | 5/6/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled.
|