Inspections for the day of: Tuesday, May 6, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01119 Final5/6/20085/6/20085/6/2008 4:21:37 PMPPASS
JAY Phone #: ###-#### ok to final
ELE08-00768 Electrical Rough-In5/5/20085/6/20085/6/2008 3:36:18 PMPPASS
ug conduit Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok to cover u/g next part from west to east stake
ELE08-00990 Conference5/6/20085/6/20085/6/2008 3:06:49 PMPDONE
We have made some changes. The riser will only be 9 inches above the tank so we changed out the pvc to ridgid and wraped it with corrision tape they would like to back fill tommorow
thanks Scott Phone #: ###-#### Internet Inspection Request from: Scott Abbott talked to contractor, see ri
ELE08-00990 Electrical Rough-In5/6/20085/6/20085/6/2008 1:59:02 PMPPASS
We have made some changes. The riser will only be 9 inches above the tank so we changed out the pvc to ridgid and wraped it with corrision tape they would like to back fill tommorow
thanks Scott Phone #: ###-#### Internet Inspection Request from: Scott Abbott ok to cover raceway at east end
ELE08-01133 Electrical Rough-In5/6/20085/6/20085/6/2008 1:39:39 PMPPASS
Phone #: ###-#### Internet Inspection Request from: David Nelson called contractor, ric ok
ELE08-00342 Rough-In Permanent Service5/6/20085/6/20085/6/2008 12:50:05 PMPPASS
taggart Phone #: ###-#### looked at new elect building, ric ok p/s u/g n ok, looked at new service on north, p/s u/g rec ok
ELE08-00770 Final5/5/20085/6/20085/6/2008 11:37:20 AMAPASS
Please call Matt with any questions. Thank you. Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa met contractor, ok to final
ELE08-01016 Rough-In Permanent Service5/5/20085/6/20085/6/2008 10:09:44 AMAPASS
Electrician on site - Gene ###-####. Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ric ok, p/s u/g n ok, 5 meters required
ELE08-00705 Electrical Rough-In5/5/20085/6/20085/6/2008 9:04:24 AMAPART
Scheduled by a contractor via Hello! on 5/5/2008 at 10:32:47 AM. Contact: ###-####. u/g ok to cover north of west building and about 20' at east of parking lot for access building area.
ELE08-01063 Final5/5/20085/6/20085/6/2008 8:24:06 AMACANC
cover inspection Phone #: ###-#### Internet Inspection Request from: Jari Rivers see ri
ELE08-01063 Electrical Rough-In5/5/20085/6/20085/6/2008 8:23:15 AMAFAIL
cover inspection Phone #: ###-#### Internet Inspection Request from: Jari Rivers called, left correction notice,NEC 680.10 PVC shall be minimum 18" deep. U/G wiring shall not be within 5' of inside wall of pool wall, 352.26 there shall not be over 4 quarter bends in raceway, 110.26(A)(3) work space shall be clear from grade, 300.5D)(4) raceway subject to damage shall be schedule 80