Inspections for the day of: Tuesday, May 6, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00162 INSP-Final Inspection5/6/20085/6/20085/7/2008 12:54:14 PMPPASS
Fire sprinkler work completed acceptable, inspection passed, permit finaled.
FIR08-00181 INSP-Final Inspection5/6/20085/6/20085/7/2008 12:49:37 PMAPASS
One horn strobe installed while on site due to low audibility levels, alarm testing passed, permit finaled.
FIR08-00216 INSP-Final Inspection5/5/20085/6/20085/7/2008 12:44:40 PMAPASS
Fire alarm work passed field testing, permit finaled.
FIR06-00595 INSP-Final Inspection5/6/20085/6/20085/7/2008 9:52:23 AMPFAIL
Inspection for elevator recall including testing lobby smoke detectors at all levels and elevator hoistway/ machine room devices. Noted shunt trip power supervision circut 20 address 122 did not report, SD 2031 is incorrectly located on the map (needs to be shown in the elevator machine room), the southeast car (elevator #3) is out of service-will need to verifiy recall at next visit, per ANSI/ASME A17.1-2000 Safety Code for Elevators- fire alarm initiating device activation in a machine room or hoistway shall cause the fire hat visual signal within the car to illuminate intermittently (2.27.3.2.6), noted SD locations at each of the four hoistways does not appear to meet requirements. Also noted spot type smoke detectors at the mechanical penthouse are not in compliance with NFPA 72 2002 sec. 5.7.3.2.1 and 5.7.3.2.4(B)(2) regarding mounting locations, beam obstructions and spacing 5.7.3.2.3 (A).
FIR08-00180 INSP-Sprinkler Rough-in/Hydro5/5/20085/6/20085/7/2008 7:26:49 AMPCANC
Overbooked
BLD08-00206 FIRE-Final Inspection5/6/20085/6/20085/6/2008 1:03:10 PMPFAIL
Post missing building address numbers, provide door to remain unlocked signage at the main entry/exit, provide current certification tag for the fire extinguisher and post as discussed, repair exit sign at the north side, provide approved hardware at two exit doors (north exit and the patio area).
FIR08-00264 INSP-Final Inspection5/5/20085/6/20085/6/2008 12:22:17 PMAPART
Overhead permit work is approved with the exception of three areas as marked on plans not yet completed at the east side including directors office SD116, open work area SD112, and conference room SD115. Provided as-built plans accepted.
FIR07-01018 FIR-Aging Inspection5/6/20085/6/20085/6/2008 11:53:22 AM DEFR
Need site inspection request
BLD06-01830 FIRE-Final Inspection5/5/20085/6/20085/6/2008 11:50:31 AMAPASS
Corrections verified for completion, fire life safety passed, NOTE: No signature card available on site at the time of inspection.
BLD08-00879 FIRE-Final Inspection5/2/20085/6/20085/5/2008 2:14:20 PMAPASS
C/N items completed