ESC09-00155
| General Inspection | 5/6/2009 | 5/6/2009 | 5/6/2009 4:15:12 PM | P | PASS |
|
|
ok
|
ELE09-00771
| Electrical Rough-In | 5/6/2009 | 5/6/2009 | 5/6/2009 4:14:26 PM | P | PART |
|
|
Greg Phone #: ###-#### r/i new kit downstairs, and ok to one side walls upstairs test kit area
|
ELE09-00649
| Final | 5/6/2009 | 5/6/2009 | 5/6/2009 3:45:48 PM | P | PASS |
|
|
This will be for a re-inspection on the final.Please contact Ron before the inspection ###-####.he will meet you at the job site.Thanks. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw ok card signed
|
ELE09-00150
| Electrical Rough-In | 5/6/2009 | 5/6/2009 | 5/6/2009 3:05:03 PM | P | PART |
|
|
mike - wall and cover on 3rd floor Phone #: ###-#### ok anop
|
ELE09-00759
| Rough-In Permanent Service | 5/5/2009 | 5/6/2009 | 5/6/2009 2:00:33 PM | P | PART |
|
|
Ok for Id Pwer to re-connect. Randy ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletche see addes p/s needs bond bushing on meterbase emt, 300.10&12 shall maintain electrical and mechanical continuity of raceway, nipple between meter and p/s
|
ELE09-00759
| Permanent Service | 5/6/2009 | 5/6/2009 | 5/6/2009 1:58:19 PM | P | PASS |
|
|
Ok for Id Pwer to re-connect. Randy ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher p/s u/g rec. ok
|
ELE09-00762
| Conference | 5/5/2009 | 5/6/2009 | 5/6/2009 1:05:10 PM | P | PART |
|
|
meet for requirements Phone #: ###-#### Internet Inspection Request from: gary batten ok talked with contr noted shall have required grds or bonds to water system, clearence for p/s and subpanel, 110.26(F)(1&2), shall address wiring for range and dryer 4wire circuit , recept, pigtail if fed from subpanel
|
ELE09-00770
| Final | 5/6/2009 | 5/6/2009 | 5/6/2009 10:53:56 AM | A | CANC |
|
|
call first Phone #: ###-#### Internet Inspection Request from: PAT MILLER contr called
|
ELE09-00769
| Final | 5/6/2009 | 5/6/2009 | 5/6/2009 10:50:21 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: PAT MILLER ok
|
ELE09-00769
| Electrical Rough-In | 5/6/2009 | 5/6/2009 | 5/6/2009 10:49:40 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: PAT MILLER ok
|
ESC09-00053
| General Inspection | 5/6/2009 | 5/6/2009 | 5/6/2009 10:11:53 AM | A | PASS |
|
|
ok
|
ELE09-00767
| Rough-In Permanent Service | 5/5/2009 | 5/6/2009 | 5/6/2009 10:11:16 AM | A | PART |
|
|
john Phone #: ###-#### see added r/r corr for p/s called bond screw theads stripped, 230.24 needs 18" from roof to drip loose, 250.52 0r 104 (A)(1) grd or bond p/s too water piping
|
ELE09-00767
| Electrical Rough-In | 5/6/2009 | 5/6/2009 | 5/6/2009 10:08:37 AM | A | PASS |
|
|
john Phone #: ###-#### r/i ok
|
ELE09-00655
| Conference | 5/5/2009 | 5/6/2009 | 5/6/2009 9:45:32 AM | A | PART |
|
|
Hawk- call to set up time to meet Phone #: ###-#### called answered owner's questions
|
ESC09-00083
| General Inspection | 5/6/2009 | 5/6/2009 | 5/6/2009 8:56:48 AM | A | FAIL |
|
|
alan ###-#### called RP told him hard surfaces need cleaning , he will address problem, and call me when corrected
|
ELE09-00741
| Temporary Service | 5/5/2009 | 5/6/2009 | 5/6/2009 8:52:01 AM | A | PASS |
|
|
Warren Phone #: ###-#### t/s u/g new ok
|
ELE09-00676
| Electrical Rough-In | 5/5/2009 | 5/6/2009 | 5/6/2009 8:23:01 AM | A | FAIL |
|
|
underground//Jared ###-#### called u/g covered before inspection corr.
|