Inspections for the day of: Wednesday, May 6, 2009.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-01144 FIRE-Final Inspection5/6/20095/6/20095/6/2009 5:57:51 PMPNR
Per conversation with contractor, project is not ready for final approval at this time due to missing doors and hardware.
BLD08-02383 FIRE-Final Inspection5/5/20095/6/20095/6/2009 5:54:45 PMAFAIL
Project related fire alarm and one attatched sprinkler permit are not ready for final at this time.
FIR09-00115 INSP-Final Inspection5/6/20095/6/20095/6/2009 5:53:32 PMAFAIL
Mixed response heads at the 2nd level ceiling above the front entry area need to match remainder of quick response heads provided at the remodel area.
BLD09-00572 FIRE-Final Inspection5/5/20095/6/20095/6/2009 5:51:34 PMAFAIL
Need to provide a current certification tag for the fire extinguisher and mount on the wall as discussed, repair one existing EM light, provide approved hardware at the back exit or remove the sign above the door.
FIR09-00182 INSP-Final Inspection5/5/20095/6/20095/6/2009 5:49:45 PMAFAIL
All three duct detectors failed to shut down HVAC units, notification devices at the second floor are not in sync, elevator hat does not flash upon machine room initiating device activation, voltage monitor for shunt trip is not provided for at the FACP, missing notification at one conference room on the 1st floor, overspacing at the elevator lobby and breakroom, notification at the 1st floor not tested due to adjustments to be made.
FIR09-00278 INSP-Conference5/6/20095/6/20095/6/2009 5:45:04 PMAPASS
Scope of fire sprinkler work okayed for final, missing fire stop installed while on site.
FIR09-00259 INSP-Final Inspection5/6/20095/6/20095/6/2009 5:41:38 PMAPASS
Fire sprinkler permit work approved for final.
FIR09-00127 INSP-Final Inspection5/6/20095/6/20095/6/2009 5:40:38 PMAPASS
Fire sprinkler permit work passed final inspection, alarm interconnections tested okay.