Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00349 INSP-Conference4/30/20094/30/2009 P 
Jeff; Phone ###-####
FIR09-00247 INSP-Sprinkler Rough-in/Hydro5/5/20095/6/20095/7/2009 8:34:00 AMPPART
The sprinkler piping above the office/lobby/storage areas are ok to cover
BLD08-02380 FIRE-Final Inspection5/6/20095/6/20095/6/2009 12:54:48 PMPFAIL
Provide lever hardware for the west front exit door and the main exit door as discussed. Remove the deadbolt from the rear exit door.
FIR08-00855 INSP-Sprinkler Rough-in/Hydro5/5/20095/6/20095/6/2009 12:53:37 PMAPART
Both of the above ground hydro tests failed. The wet system had visable leakage on the mezzanine. The FDC was not part of the hydro test and wil need to be included as per NFPA 13. The corrections noted on the previous inspection have been corrected and the remaining piping can be covered.
BLD09-00103 FIRE-Final Inspection5/5/20095/6/20095/6/2009 9:59:09 AMAPASS
Life safety passed.
BLD09-00622 FIRE-Final Inspection5/5/20095/6/20095/6/2009 9:58:44 AMAPART
A temporary occupancy wasa given until the thumbturn locks are removed from the front and rear exit doors, a sticker "Door to remain ........" is provided at the front door, single action hardware is provided on the rear exit door, emergency lighting is provided at the existing exit signs and a permit is provided/required for the existing alarm system that has been removed. Per phone discussion with the fire alarm plan reviewer this occupancy does not require a fire alarm system and per FIR04-00414 this system was initially installed voluntarily.
FIR09-00177 INSP-Sprinkler Rough-in/Hydro5/5/20095/6/20095/5/2009 3:14:47 PMACANC
Rob Claborn Phone #: ###-#### Internet Inspection Request from: John Warnick Inspection cancelled from web by: John Warnick