ELE10-00974
| Temporary Service | 5/5/2010 | 5/6/2010 | 5/7/2010 6:21:41 AM | P | CANC |
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### see 5/7/10
|
ELE10-00981
| Temporary Service | 5/5/2010 | 5/6/2010 | 5/7/2010 6:21:00 AM | A | CANC |
|
|
Dino-Please call prior to inspection Phone #: ###-#### see 5/7/10
|
ELE10-00979
| Temporary Service | 5/5/2010 | 5/6/2010 | 5/6/2010 4:58:35 PM | A | FAIL |
|
|
warren Phone #: ###-#### called, left message, NEC 400.5 so cord only rated at 45A, 250.92 shall wire in bond bushing, 312.5 shall provide abrasion protection, 200.7 shall identify grounded conductor, 110.14 shall ensure tight connections, BCC shall post job id sticker, Note; corrections shall be made within 5 working days or further action will be taken
|
ELE10-00973
| Temporary Service | 5/5/2010 | 5/6/2010 | 5/6/2010 2:37:50 PM | P | PASS |
|
|
Inspection requested from web by: Stephen Kren Phone #: ###-#### t/s u/g n ok
|
ELE10-00982
| Electrical Rough-In | 5/6/2010 | 5/6/2010 | 5/6/2010 1:12:01 PM | P | PASS |
|
|
Jim Phone #: ###-#### ric ok
|
ELE10-00420
| Final | 5/5/2010 | 5/6/2010 | 5/6/2010 12:38:20 PM | P | CANC |
|
|
Julia Marsh owner ###-####, Mike ###-#### contractor (1/2 hr notice), I will be out of the area, gate code #2500, pathway around back to basement. called, contractor asked to cancel till next week This is the same request I made yesterday, What happened? Inspection requested from web by: Andy Derrick Phone #: ###-####
|
ELE10-00963
| Permanent Service | 5/4/2010 | 5/6/2010 | 5/6/2010 12:31:35 PM | P | PASS |
|
|
PAUL SERVICE INSPECTION EARLY PM IF POSSIBLE Inspection requested from web by: Sean DeLacy Phone #: ###-#### p/s o/h rec ok
|
ELE10-00972
| Electrical Rough-In | 5/6/2010 | 5/6/2010 | 5/6/2010 12:21:45 PM | P | PASS |
|
|
ed - early afternoon please Phone #: ###-#### ric ok
|
ELE10-00975
| Final | 5/5/2010 | 5/6/2010 | 5/6/2010 11:33:59 AM | A | PASS |
|
|
Please call Dennis to gain access to building ###-#### Thank You Inspection requested from web by: Todd Holbrook ok to final, signed card
|
ELE10-00951
| Electrical Rough-In | 5/6/2010 | 5/6/2010 | 5/6/2010 10:05:10 AM | A | PASS |
|
|
liock box is by garage man door code is 7828 Inspection requested from web by: Shaun Kirkman Phone #: ###-#### ric ok
|
ELE10-00506
| Final | 5/5/2010 | 5/6/2010 | 5/6/2010 10:04:08 AM | A | PASS |
|
|
Inspection requested from web by: Joe Thomas Phone #: ###-#### ok to final
|
ELE10-00971
| Rough-In Permanent Service | 5/5/2010 | 5/6/2010 | 5/6/2010 9:37:01 AM | A | FAIL |
|
|
Inspection requested from web by: daniel bibikov Phone #: ###-#### called, left correction notice, NEC 250.94 shall provide intersystem bond bar, 250.92 shall provide bond bushings, 314.4 shall ground metal boxes, 314.20 boxes shall be flush with finished surface of combustible material, 314.16 shall provide free space for conductors-box fill-metal box, 230.6 service conductors considered outside when encased in 2" concrete, NOTE: corrections shall be made in 5 working days or further action will be taken
|
ELE10-00972
| Rough-In Permanent Service | 5/5/2010 | 5/6/2010 | 5/6/2010 8:49:28 AM | A | NH |
|
|
ed Phone #: ###-#### called to reschedule
|
ELE10-00726
| Final | 5/5/2010 | 5/6/2010 | 5/6/2010 8:26:13 AM | A | PART |
|
|
This if for the cubicles for phase 1. I will be there by 8:15 Thanks, Ron Inspection requested from web by: Ron Zimmerman Phone #: ###-#### ok to final phase 1 cubicles
|
ELE10-00951
| Final | 5/6/2010 | 5/6/2010 | 5/6/2010 7:17:31 AM | A | CANC |
|
|
Key is in lock box by garage code is 7828 Inspection requested from web by: Shaun Kirkman Phone #: ###-#### Inspection cancelled from web by: Shaun Kirkman
|