Inspections for the day of: Thursday, May 6, 2010.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00974 Temporary Service5/5/20105/6/20105/7/2010 6:21:41 AMPCANC
Inspection requested from web by: TOM BICANDI Phone #: ###-#### see 5/7/10
ELE10-00981 Temporary Service5/5/20105/6/20105/7/2010 6:21:00 AMACANC
Dino-Please call prior to inspection Phone #: ###-#### see 5/7/10
ELE10-00979 Temporary Service5/5/20105/6/20105/6/2010 4:58:35 PMAFAIL
warren Phone #: ###-#### called, left message, NEC 400.5 so cord only rated at 45A, 250.92 shall wire in bond bushing, 312.5 shall provide abrasion protection, 200.7 shall identify grounded conductor, 110.14 shall ensure tight connections, BCC shall post job id sticker, Note; corrections shall be made within 5 working days or further action will be taken
ELE10-00973 Temporary Service5/5/20105/6/20105/6/2010 2:37:50 PMPPASS
Inspection requested from web by: Stephen Kren Phone #: ###-#### t/s u/g n ok
ELE10-00982 Electrical Rough-In5/6/20105/6/20105/6/2010 1:12:01 PMPPASS
Jim Phone #: ###-#### ric ok
ELE10-00420 Final5/5/20105/6/20105/6/2010 12:38:20 PMPCANC
Julia Marsh owner ###-####, Mike ###-#### contractor (1/2 hr notice), I will be out of the area, gate code #2500, pathway around back to basement. called, contractor asked to cancel till next week
This is the same request I made yesterday, What happened? Inspection requested from web by: Andy Derrick Phone #: ###-####
ELE10-00963 Permanent Service5/4/20105/6/20105/6/2010 12:31:35 PMPPASS
PAUL SERVICE INSPECTION EARLY PM IF POSSIBLE Inspection requested from web by: Sean DeLacy Phone #: ###-#### p/s o/h rec ok
ELE10-00972 Electrical Rough-In5/6/20105/6/20105/6/2010 12:21:45 PMPPASS
ed - early afternoon please Phone #: ###-#### ric ok
ELE10-00975 Final5/5/20105/6/20105/6/2010 11:33:59 AMAPASS
Please call Dennis to gain access to building
###-#### Thank You Inspection requested from web by: Todd Holbrook ok to final, signed card
ELE10-00951 Electrical Rough-In5/6/20105/6/20105/6/2010 10:05:10 AMAPASS
liock box is by garage man door code is 7828 Inspection requested from web by: Shaun Kirkman Phone #: ###-#### ric ok
ELE10-00506 Final5/5/20105/6/20105/6/2010 10:04:08 AMAPASS
Inspection requested from web by: Joe Thomas Phone #: ###-#### ok to final
ELE10-00971 Rough-In Permanent Service5/5/20105/6/20105/6/2010 9:37:01 AMAFAIL
Inspection requested from web by: daniel bibikov Phone #: ###-#### called, left correction notice, NEC 250.94 shall provide intersystem bond bar, 250.92 shall provide bond bushings, 314.4 shall ground metal boxes, 314.20 boxes shall be flush with finished surface of combustible material, 314.16 shall provide free space for conductors-box fill-metal box, 230.6 service conductors considered outside when encased in 2" concrete, NOTE: corrections shall be made in 5 working days or further action will be taken
ELE10-00972 Rough-In Permanent Service5/5/20105/6/20105/6/2010 8:49:28 AMANH
ed Phone #: ###-#### called to reschedule
ELE10-00726 Final5/5/20105/6/20105/6/2010 8:26:13 AMAPART
This if for the cubicles for phase 1.
I will be there by 8:15
Thanks,
Ron Inspection requested from web by: Ron Zimmerman Phone #: ###-#### ok to final phase 1 cubicles
ELE10-00951 Final5/6/20105/6/20105/6/2010 7:17:31 AMACANC
Key is in lock box by garage code is 7828 Inspection requested from web by: Shaun Kirkman Phone #: ###-#### Inspection cancelled from web by: Shaun Kirkman