Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD10-00600 FIRE-Final Inspection5/6/20105/6/20105/6/2010 3:25:53 PMPPASS
Life safety passed. No equipment has been installed yet.
BLD09-01007 FIRE-Final Inspection5/6/20105/6/20105/6/2010 2:52:04 PMPPART
A temporary occupancy was given with Scott and Marks approval until the fire alarm permit for the new tamper switch on the anti-freeze loop has been finaled. The work has been scheduled for monday morning at 8:00am.
FIR10-00188 INSP-Conference5/6/20105/6/20105/6/2010 2:51:46 PMPDONE
A temporary occupancy was given with Scott and Marks approval until this fire alarm permit for the new tamper switch on the anti-freeze loop has been finaled. The work has been scheduled for monday morning at 8:00am.
BLD09-01275 FIRE-Final Inspection5/5/20105/6/20105/6/2010 2:50:04 PMAPART
A temporary occupancy was given with Scott and Marks approval until the fire alarm permit for the new tamper switch on the anti-freeze loop has been finaled. The work has been scheduled for monday morning at 8:00am.
BLD04-00469 FIRE-Conference5/5/20105/6/20105/6/2010 11:02:47 AMADONE
I went over items completed and remaining items with Holly, Clint, Tim and the warehouse manager. All items have been corrected except on exit sign/emergency light at the south warehouse exit did not function, missing Knox Box, and possibly a racking/high piled storage permit. If a racking/storage permit is to be a voided the owner needs to keep all storage under 12', racks no higher than 8' and empty plastic water bottles less than 5'. Water filled bottles can be stored up to 12'. The racks will have to be modified to permanantly discourage placement of horizontal members above 8'. Tim Frost was consulted.
FIR07-01003 INSP-Conference5/5/20105/6/20105/6/2010 10:54:09 AMADONE
I spoke to Mike about not requiring a new permit and that this permit can be finished as long as the new work matched what was originally submitted.
BLD09-01275 FIRE-Conference5/6/20105/6/20105/6/2010 10:00:06 AMADONE
The property manager, Linda, contacted me about a temporary occupancy for this project until Monday due to SimpleGrinnell not being able to perform their work until that I deferred her to Mark Senteno for a decision.