FIR10-00137
| INSP-Final Inspection | 5/2/2011 | 5/3/2011 | | A | |
|
|
EARL Phone #: ###-####
|
FIR10-00137
| INSP-Alarm Testing | 5/4/2011 | 5/6/2011 | 5/6/2011 5:48:59 PM | A | PART |
|
|
Issues noted today include DD trouble which supercedes supervisory condition for unit shutdown, non-latching ID smoke detectors, dampers at some basement ducts are not functional including L2S019 and L2S020, TS at the sprinkler riser are latching," AC power on" lamp at the panel remains illuminated during power off condition.
|
BLD10-02149
| FIRE-Conference | 5/6/2011 | 5/6/2011 | 5/6/2011 5:32:46 PM | P | DONE |
|
|
Items discussed with contractor include certification tag for the fire extinguisher, repair directional exit sign on alternate power source, provide approved door hardware at the restrooms and the security gate from the pool enclosure, missing stamped plans on site.
|
FIR10-00659
| INSP-Supply line flush | 5/6/2011 | 5/6/2011 | 5/6/2011 5:23:31 PM | P | DONE |
|
|
UG supply line flush completed satisfactory.
|
BLD11-00221
| FIRE-Final Inspection | 5/5/2011 | 5/6/2011 | 5/6/2011 11:55:20 AM | A | PASS |
|
|
Reinspection passed, correction items completed. Fire life safety finaled.
|
BLD10-02926
| FIRE-Final Inspection | 5/5/2011 | 5/6/2011 | 5/6/2011 11:53:40 AM | A | PASS |
|
|
Corrections finished. Fire life safety passed.
|