Inspections for the day of: Tuesday, May 6, 2014.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00882 Rough-In Permanent Service5/6/20145/6/20145/7/2014 3:00:49 PMPPASS
Phone #: ###-#### >> Inspection requested via web by David Nelson checked with pool builder, their electrical contractor is ISquared, they will have them get city permit, ri ok, p/s u/g n ok
ELE14-00570 Electrical Rough-In5/5/20145/6/20145/6/2014 2:52:16 PMPCANC
michael Phone #: ###-#### see conf
ELE14-00570 Conference5/6/20145/6/20145/6/2014 2:51:36 PMPDONE
michael Phone #: ###-#### reviewed make-up, outlet spacing, stapling, 1 1/4", circuiting, free length conductor, empty house
ELE14-01053 Final5/6/20145/6/20145/6/2014 2:04:51 PMPPASS
Matt. Call prior to heading to the site. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy ok final
ELE12-00764 Final5/5/20145/6/20145/6/2014 1:04:16 PMPCANC
Darlene Phone #: ###-#### see ri
ELE12-00764 Electrical Rough-In5/6/20145/6/20145/6/2014 1:03:35 PMPFAIL
Darlene Phone #: ###-#### met owner, left correction notice, NEC 300.4(A)(C) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 334.30 nm cable shall be stapled within 12" of box or 314.17(C) 8" if more than 1 cable, 210.52(A) shall install receptacles within 6' of entry and 12' maximum between receptacles, BCC shall not install devices until ri complete so free length of conductor can be inspected
ELE14-00780 Final5/5/20145/6/20145/6/2014 10:34:06 AMANR
Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot called, dishwasher and disposal not installed, switch cover missing and loose gfci in womens room , will recall
ELE14-00465 Final5/6/20145/6/20145/6/2014 9:53:30 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn ok final
ELE14-00548 Final5/6/20145/6/20145/6/2014 9:31:08 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn called, power to a/c receptacle not on, 2 breakers tripping #16, #18 faulted
ELE14-01018 Electrical Rough-In5/5/20145/6/20145/6/2014 8:56:21 AMAPASS
Call ###-#### for access code Phone #: ###-#### >> Inspection requested via web by David Nelson ri ok
ELE14-01123 Rough-In Permanent Service5/6/20145/6/20145/6/2014 8:16:33 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok