BLD14-03504
| FIRE-Final Inspection | 5/6/2015 | 5/6/2015 | 5/6/2015 3:21:57 PM | P | PASS |
|
|
life safety passed
|
FIR15-00058
| INSP-Final Inspection | 5/6/2015 | 5/6/2015 | 5/6/2015 3:20:52 PM | P | PASS |
|
|
permit finaled
|
FIR15-00173
| INSP-Sprinkler Rough-in | 5/6/2015 | 5/6/2015 | 5/6/2015 3:01:19 PM | P | PART |
|
|
All piping can be covered except where the new and modified soffits have been installed. These areas need to have fire protection or meet an exception
|
BLD14-03579
| FIRE-Final Inspection | 5/4/2015 | 5/6/2015 | 5/6/2015 2:53:48 PM | P | PASS |
|
|
fire/life safety passed. The two exit discharge lights and two emergency can lights to be repaired prior to a building inspection sign off. Also provide verification to the building inspector that the thumbturn deadbolts provided on the restroom doors meets ADA
|
FIR15-00224
| INSP-Sprinkler Rough-in | 5/6/2015 | 5/6/2015 | 5/6/2015 1:50:39 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR15-00302
| INSP-Final Inspection | 5/5/2015 | 5/6/2015 | 5/6/2015 1:47:50 PM | A | PASS |
|
|
Permit finaled
|
FIR14-00460
| INSP-Final Inspection | 5/6/2015 | 5/6/2015 | 5/6/2015 1:28:02 PM | P | PASS |
|
|
Final previously performed with Tim Frost.
|
FIR14-00762
| INSP-Sprinkler Rough-in | 5/5/2015 | 5/6/2015 | 5/6/2015 12:27:46 PM | A | PASS |
|
|
Piping rough-in and tenting inspection passed. Piping can be covered.
|
FIR14-00902
| INSP-Final Inspection | 5/5/2015 | 5/6/2015 | 5/6/2015 10:51:24 AM | A | PASS |
|
|
Permit finaled
|
BLD14-03516
| FIRE-Final Inspection | 5/5/2015 | 5/6/2015 | 5/6/2015 10:06:53 AM | A | PASS |
|
|
life safety passed
|
NAF15-00006
| INSP-Sprinkler Rough-in/Hydro | 5/5/2015 | 5/6/2015 | 5/6/2015 9:12:09 AM | A | FAIL |
|
|
First floor hydro test failed due to visible loss on guage.
|
NAF14-00028
| INSP-Sprinkler Rough-in/Hydro | 5/5/2015 | 5/6/2015 | 5/6/2015 9:10:12 AM | A | FAIL |
|
|
Hydro Underground failded due to visible leak at guage
|
BLD15-01028
| FIRE-Final Inspection | 5/5/2015 | 5/6/2015 | 5/6/2015 8:10:18 AM | A | PASS |
|
|
Life safety passed. Single action hardware to be installed prior to the building inspection
|
BLD15-00261
| FIRE-Final Inspection | 5/5/2015 | 5/6/2015 | 5/6/2015 8:01:06 AM | P | CANC |
|
|
No life safety sign off required.
|
FIR15-00301
| INSP-Sprinkler Rough-in/Hydro | 5/5/2015 | 5/6/2015 | 5/5/2015 2:19:08 PM | P | CANC |
|
|