ELE11-01976
| ELE-Aging Inspection | 5/6/2015 | 5/6/2015 | 5/13/2015 10:57:03 AM | | DONE |
|
|
contractor said it`s on the list to complete.
|
ELE13-01291
| Conference | 5/5/2015 | 5/6/2015 | 5/6/2015 12:04:28 PM | A | DONE |
|
|
Contact Tony Keen in job trailer for Fire Pump Controller consultation. Phone #: ###-#### Inspection requested via web by Tom Betty Discussed fire pump controller provides short circuit protection only as per 695.5(C)(2) requirement. Waiting for Eaton`s electrical engineer (Rick Dottson) to sign off that MCP will operate indefinitely under locked rotor conditions.
|
ELE15-01312
| Conference | 5/5/2015 | 5/6/2015 | 5/6/2015 9:29:52 AM | A | DONE |
|
|
Alex Phone #: ###-#### Spoke with homeowner about electrical requirements of wiring detached garage.
|
ELE14-03108
| ELE-Request for Extension | 5/5/2015 | 5/6/2015 | 5/6/2015 8:26:11 AM | A | PASS |
|
|
Emily Phone #: ###-#### Extension ok
|
ELE15-01305
| Temporary Service | 5/4/2015 | 5/6/2015 | 5/5/2015 6:53:11 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman Inspection cancelled from web by: Emmet Bushman
|