FIR14-00529
| INSP-Final Inspection | 5/5/2015 | 5/6/2015 | 5/6/2015 5:37:25 PM | P | FAIL |
|
|
Flow test requirements were not met for riser 4, requires acceleration device. Water flow timed at 66 seconds, requirement for 4 outlet manifold is 40 seconds. Riser 3 passed with 37 second flow.
|
FIR15-00301
| INSP-Final Inspection | 5/5/2015 | 5/6/2015 | 5/6/2015 5:35:52 PM | P | PART |
|
|
Partial final pass. Functional alarm test complete with the exception of flow switches on risers 1 & 2. Prior to final the following items to be completed: provide updated plans, provide knox box, provide document box, "Fire Alarm Control Panel" signage on doors, floor plan with initiating devices posted at FACP, and repaint alarm bell and add call 911 when sounding verbage.
|
BLD15-00113
| FIRE-Final Inspection | 5/5/2015 | 5/6/2015 | 5/6/2015 5:23:31 PM | P | PASS |
|
|
Fire life safety pass
|
FIR15-00107
| INSP-Sprinkler Rough-in/Hydro | 5/5/2015 | 5/6/2015 | 5/6/2015 4:01:22 PM | A | PASS |
|
|
Sprinkler system addition from 4" main to new bays was isolated and hydrostatic test passed. Rough-in complete.
Field verified appropriate use of 12 high temperature heads within 7' of radiant heaters.
Changes in field were made, resubmittal is under review. Per phone call with Tim Frost, storage room ok.
|
FIR15-00154
| INSP-Final Inspection | 5/6/2015 | 5/6/2015 | 5/6/2015 3:34:59 PM | P | PASS |
|
|
Scope of work complete. Permit finaled.
|
BLD11-00961
| FIRE-Final Inspection | 5/5/2015 | 5/6/2015 | 5/6/2015 2:05:59 PM | A | PASS |
|
|
Fire life safety pass. Aging permit; inspection completed in line with BLD 15-00889 inspection.
|
BLD14-02471
| FIRE-Conference | 5/5/2015 | 5/6/2015 | 5/6/2015 12:50:58 PM | A | DONE |
|
|
Walk through with Mike. Discussed life safety items to include exit signs, door hardware, fire extinguishers. Also discussed need for sprinkler underground flush, rough-in and hydrostatic test inspections.
|
FIR15-00082
| INSP-Sprinkler Rough-in/Hydro | 5/5/2015 | 5/6/2015 | 5/6/2015 10:49:43 AM | A | PASS |
|
|
1st floor hydrostatic test passed.
|