Inspections for the day of: Monday, May 6, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-00107 ELE-Aging Inspection5/6/20195/6/20195/7/2019 9:43:05 AM DONE
see final
ELE19-01643 Final5/6/20195/6/20195/6/2019 3:43:00 PMPNR
Phone #: ###-#### Inspection requested via web by Jim Williams Not ready for final at this time
ELE19-01643 Permanent Service5/6/20195/6/20195/6/2019 3:42:05 PMPPART
Phone #: ###-#### Inspection requested via web by Jim Williams Emergency power conntection completed over the weekend. 5 working days to start the procees to correct code violations with service panel. NEC 408.38 No Dead front on service panel, NEC 314.17(B) Conductor entering enclosure without abrasion protection. Branch circuit raceway not attached to enclosure. Neutrals and grounds terminated under same lugs. Branch circuits doubled up on circuit breakers.Ocd for A/C unit over sized. update grounding system. Complete directory. Existing service installed without inspection, current NEC applies.
ELE19-00602 Electrical Rough-In5/6/20195/6/20195/6/2019 1:40:24 PMPPASS
UG cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Rough-in ok cover between A-D 1 thur 9
ELE17-01854 Final5/6/20195/6/20195/6/2019 1:15:43 PMPPASS
Job conplete, Final ok
ELE18-02199 Final5/6/20195/6/20195/6/2019 9:20:53 AMAPASS
Temp. service final ok
ELE18-02197 Final5/6/20195/6/20195/6/2019 9:20:00 AMAPASS
Temp service final ok
ELE18-02228 Final5/6/20195/6/20195/6/2019 9:17:05 AMAPASS
Job complete, Final ok