Inspections for the day of: Wednesday, May 7, 2003.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-00116 Final5/6/20035/7/20035/7/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 5/6/2003 at 1:56:51 PM. Contact: ###-####. ok card signed ok for ceiling cover also 5/7/2003 9:00:09 AM
ELE03-01314 Electrical Rough-In5/6/20035/7/20035/7/2003 12:00:00 AMAFAIL
JIM; Phone #: ###-#### Internet Inspection Request from: Darla Downs PLEASE COME AROUND TO THE BACK OF THE HOUSE TO ENTER cor. posted called left message,210.52(A) needs outlet for wall space between slider and garage door, 300.4 (D) 11/4, 314.43 no screws allowed in non metallic boxes 5/7/2003 10:11:33 AM
ELE02-03829 Final5/7/20035/7/20035/7/2003 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Cathy Felin ok 5/7/2003 2:30:47 PM
ELE03-00923 Electrical Rough-In5/7/20035/7/20035/7/2003 12:00:00 AMPPART
Phone #: ###-#### Internet Inspection Request from: Darla Downs concrete cover for electrode ok 5/7/2003 4:06:21 PM
ELE03-00557 Final5/7/20035/7/20035/7/2003 12:00:00 AMPNR
###-#### BRIAN needs to move sprinkler control for clearence in front of panel recepts not secure, wire D W or terminate mc in box called con tractor 5/7/2003 1:44:33 PM
ELE03-01282 Electrical Rough-In5/6/20035/7/20035/7/2003 12:00:00 AMPPASS
shane ###-####; Phone #: ###-#### Internet Inspection Request from: Annette Moore r/i ok needs 15 amp circuit to hydro tub owner will call for r/i when ready 5/7/2003 3:30:15 PM