FIR04-00089
| INSP-Alarm Testing | 5/5/2004 | 5/7/2004 | 5/7/2004 12:00:00 AM | A | PASS |
|
|
fire alarm finaled 5/7/2004 10:00:43 AM
|
BLD04-00291
| FIRE-Final Inspection | 5/6/2004 | 5/7/2004 | 5/7/2004 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 5/7/2004 8:16:04 AM
|
FIR04-00005
| INSP-Final Inspection | 5/6/2004 | 5/7/2004 | 5/7/2004 12:00:00 AM | A | PASS |
|
|
fire sprinkler finaled 5/7/2004 12:51:15 PM
|
FIR04-00264
| INSP-Final Inspection | 5/6/2004 | 5/7/2004 | 5/7/2004 12:00:00 AM | A | PASS |
|
|
Fire sprinklers finaled. Hanger not required to be upgraded to code compliance per Dave Miller 5/7/2004 1:52:41 PM
|
BLD04-00222
| BLD-Conference | 5/7/2004 | 5/7/2004 | 5/7/2004 12:00:00 AM | P | FAIL |
|
|
final fire alarm permit. final sprinkler permit. Remove thumbturn at main exit and provide "Door to remain unlocked while building is occupied" sticker 5/7/2004 3:49:19 PM
|
FIR04-00213
| INSP-Final Inspection | 5/7/2004 | 5/7/2004 | 5/7/2004 12:00:00 AM | P | FAIL |
|
|
Insulation is still falling from the deck and blocking upright sprinkler heads
|
BLD04-00788
| FIRE-Final Inspection | 5/7/2004 | 5/7/2004 | 5/7/2004 12:00:00 AM | P | FAIL |
|
|
Provide emergency lighting as per approved plans. Repair exit signs. Test the exhaust system. Provide fire extinguishers per review note #13. Provide ADA hardware on all doors.
|
BLD04-00318
| FIRE-Final Inspection | 5/7/2004 | 5/7/2004 | 5/7/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety for demolition Ok
|