ELE07-01623
| Electrical Rough-In | 5/4/2007 | 5/7/2007 | 5/7/2007 3:33:35 PM | P | PASS |
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ri ok, see final
|
ELE07-01623
| Final | 5/7/2007 | 5/7/2007 | 5/7/2007 3:32:59 PM | P | PASS |
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final
|
ELE07-01563
| Electrical Rough-In | 5/7/2007 | 5/7/2007 | 5/7/2007 2:56:57 PM | P | PASS |
|
|
Tim ; Phone #: ###-#### Internet Inspection Request from: Darla Downs ric ok
|
ELE07-01636
| Electrical Rough-In | 5/7/2007 | 5/7/2007 | 5/7/2007 2:12:52 PM | P | NR |
|
|
please inspect service repair and miscellaneous punch list items Phone #: ###-#### x0000 Internet Inspection Request from: BRIAN KEITH met elect, told BCC concrete encased electrode shall be ready to pour; clean and formed to accept min 2" concrete all around gec
|
ELE07-01635
| Temporary Service | 5/7/2007 | 5/7/2007 | 5/7/2007 1:37:52 PM | P | PASS |
|
|
john ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith t/s o/h n ok
|
ELE07-01622
| Permanent Service | 5/7/2007 | 5/7/2007 | 5/7/2007 1:01:08 PM | P | PASS |
|
|
mark ; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s o/h rec ok
|
ELE07-01586
| Electrical Rough-In | 5/7/2007 | 5/7/2007 | 5/7/2007 12:30:19 PM | P | PASS |
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover new walls only
|
ELE07-01551
| Electrical Rough-In | 5/4/2007 | 5/7/2007 | 5/7/2007 11:43:49 AM | A | PASS |
|
|
joe - 3rd floor ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith 3rd floor rooms anop ok to cover
|
ELE07-01584
| Permanent Service | 5/4/2007 | 5/7/2007 | 5/7/2007 10:28:06 AM | A | PASS |
|
|
100amp service upgrade, house is vacant and door will be open, any questions call George @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose p/s o/h rec ok
|
ELE07-01577
| Electrical Rough-In | 5/7/2007 | 5/7/2007 | 5/7/2007 9:54:52 AM | A | PASS |
|
|
corrections made, ok to pour equipotential plane
|
ELE07-01577
| Permanent Service | 5/4/2007 | 5/7/2007 | 5/7/2007 9:52:03 AM | A | CANC |
|
|
Re-inspection Equi-potential Bonding - Swimming Pool Deck Replacement (Failed 5/04 AM) .. contact Kelly @ ###-#### or Rick @ ###-#### Phone #: ###-#### Internet Inspection Request from: Kelly Felin
|
ELE06-04578
| Final | 5/6/2007 | 5/7/2007 | 5/7/2007 9:24:40 AM | A | PASS |
|
|
Please call when 10 minutes away so we can meet. Final for kitchen as well as bedroom and bathroom. Phone #: ###-#### Internet Inspection Request from: steven sewell ok to final
|
ELE07-01586
| Electrical Rough-In | 5/4/2007 | 5/7/2007 | 5/7/2007 8:51:18 AM | A | FAIL |
|
|
chris ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left corr notice to owner and elect contr, BCC no violations shall be retained for electrical: obvious, but not all inclusive until opened up violations appear to be: open boxes in ceiling, mc cable and emt not strapped, abandoned wiring in ceiling, outlets above ceiling, wiring on grid, foreign piping systems over panels, work space about electrical equipment not sufficient, redundant grounding for patient care areas not provided, no access to parts of job, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members
|
ELE07-01196
| Final | 5/7/2007 | 5/7/2007 | 5/7/2007 7:57:02 AM | A | PART |
|
|
Please call 1/2 hour before inspection. Call Fred. Phone #: ###-#### Internet Inspection Request from: Todd Sellman met contr, called contr, left correction notice- electrical work completed for vanilla finish but attached bld is for completed installation see bld07-00134 therefore no completed inspection, no card signed.
|