Inspections for the day of: Monday, May 7, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01623 Electrical Rough-In5/4/20075/7/20075/7/2007 3:33:35 PMPPASS
brian; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ri ok, see final
ELE07-01623 Final5/7/20075/7/20075/7/2007 3:32:59 PMPPASS
brian; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final
ELE07-01563 Electrical Rough-In5/7/20075/7/20075/7/2007 2:56:57 PMPPASS
Tim ; Phone #: ###-#### Internet Inspection Request from: Darla Downs ric ok
ELE07-01636 Electrical Rough-In5/7/20075/7/20075/7/2007 2:12:52 PMPNR
please inspect service repair and miscellaneous punch list items
Phone #: ###-#### x0000 Internet Inspection Request from: BRIAN KEITH met elect, told BCC concrete encased electrode shall be ready to pour; clean and formed to accept min 2" concrete all around gec
ELE07-01635 Temporary Service5/7/20075/7/20075/7/2007 1:37:52 PMPPASS
john ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith t/s o/h n ok
ELE07-01622 Permanent Service5/7/20075/7/20075/7/2007 1:01:08 PMPPASS
mark ; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s o/h rec ok
ELE07-01586 Electrical Rough-In5/7/20075/7/20075/7/2007 12:30:19 PMPPASS
chris; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to cover new walls only
ELE07-01551 Electrical Rough-In5/4/20075/7/20075/7/2007 11:43:49 AMAPASS
joe - 3rd floor ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith 3rd floor rooms anop ok to cover
ELE07-01584 Permanent Service5/4/20075/7/20075/7/2007 10:28:06 AMAPASS
100amp service upgrade, house is vacant and door will be open, any questions call George @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose p/s o/h rec ok
ELE07-01577 Electrical Rough-In5/7/20075/7/20075/7/2007 9:54:52 AMAPASS
corrections made, ok to pour equipotential plane
ELE07-01577 Permanent Service5/4/20075/7/20075/7/2007 9:52:03 AMACANC
Re-inspection Equi-potential Bonding - Swimming Pool Deck Replacement (Failed 5/04 AM) .. contact Kelly @ ###-#### or Rick @ ###-#### Phone #: ###-#### Internet Inspection Request from: Kelly Felin
ELE06-04578 Final5/6/20075/7/20075/7/2007 9:24:40 AMAPASS
Please call when 10 minutes away so we can meet. Final for kitchen as well as bedroom and bathroom. Phone #: ###-#### Internet Inspection Request from: steven sewell ok to final
ELE07-01586 Electrical Rough-In5/4/20075/7/20075/7/2007 8:51:18 AMAFAIL
chris ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left corr notice to owner and elect contr, BCC no violations shall be retained for electrical: obvious, but not all inclusive until opened up violations appear to be: open boxes in ceiling, mc cable and emt not strapped, abandoned wiring in ceiling, outlets above ceiling, wiring on grid, foreign piping systems over panels, work space about electrical equipment not sufficient, redundant grounding for patient care areas not provided, no access to parts of job, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members
ELE07-01196 Final5/7/20075/7/20075/7/2007 7:57:02 AMAPART
Please call 1/2 hour before inspection. Call Fred. Phone #: ###-#### Internet Inspection Request from: Todd Sellman met contr, called contr, left correction notice- electrical work completed for vanilla finish but attached bld is for completed installation see bld07-00134 therefore no completed inspection, no card signed.