ELE06-04413
| Electrical Rough-In | 5/6/2008 | 5/7/2008 | 5/7/2008 4:02:17 PM | P | PASS |
|
|
Cover inspection for bath floor heat mat. Inspection for as late as possible in the afternoon please. Thank you! Phone #: ###-#### Internet Inspection Request from: Adam Staigle ok to cover floor heat in bathroom
|
ELE08-00283
| ELE-Aging Inspection | 5/7/2008 | 5/7/2008 | 5/7/2008 3:24:20 PM | | DONE |
|
|
called contractor, left message to call back for location and to request his inspection
|
ELE08-00154
| ELE-Aging Inspection | 5/7/2008 | 5/7/2008 | 5/7/2008 3:06:28 PM | | DONE |
|
|
looked at job, see final
|
ELE08-00154
| Final | 5/7/2008 | 5/7/2008 | 5/7/2008 2:22:11 PM | P | PASS |
|
|
looked at installation, ok to final
|
ELE08-00993
| Final | 5/7/2008 | 5/7/2008 | 5/7/2008 2:17:05 PM | P | PASS |
|
|
PAUL Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to final, signed occupancy card
|
ELE08-00507
| Electrical Rough-In | 5/6/2008 | 5/7/2008 | 5/7/2008 1:15:26 PM | P | PART |
|
|
larry - partial for bathroom and framed walls Phone #: ###-#### ok to cover walls and hard lids only anop
|
ELE08-01140
| Permanent Service | 5/6/2008 | 5/7/2008 | 5/7/2008 10:26:44 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams see conference
|
ELE08-01140
| Conference | 5/7/2008 | 5/7/2008 | 5/7/2008 10:26:20 AM | A | DONE |
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams met contractor, talked about sub-panel clearance requirements and piping interferences for basement panel, rest ok, will recall for p/s
|
ELE08-01063
| Electrical Rough-In | 5/6/2008 | 5/7/2008 | 5/7/2008 10:07:00 AM | A | PASS |
|
|
reinspection Phone #: ###-#### Internet Inspection Request from: Jari Rivers u/g only ok to cover, corrections made
|
ELE08-01139
| Final | 5/7/2008 | 5/7/2008 | 5/7/2008 9:46:43 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 5/7/2008 at 6:55:10 AM. Contact: ###-####. called, left correction notice, BCC shall affix job id sticker, NEC 310.8(D) insulated conductors exposed to sunlight shall be listed as being sunlight resistant, 408.8 panel shall be dead-front, 230.66 disconnect shall be marked as suitable for service entrance equipment, NOTE: need to see pump and controller
|
ELE08-00442
| Final | 5/7/2008 | 5/7/2008 | 5/7/2008 9:30:39 AM | P | CANC |
|
|
contact: Shane Korte Phone #: ###-#### Internet Inspection Request from: Deb Gooden Inspection cancelled from web by: Deb Gooden
|
ELE08-01092
| Electrical Rough-In | 5/6/2008 | 5/7/2008 | 5/7/2008 8:56:37 AM | A | FAIL |
|
|
This is a swimming pool. The inspection needed is underground. Phone #: ###-#### Internet Inspection Request from: Chris Weimar called contractor, left correction notice, NEC 680.10 underground raceways shall be 18" deep within 5' of inside wall of pool
|
ELE08-01120
| Electrical Rough-In | 5/6/2008 | 5/7/2008 | 5/7/2008 8:05:08 AM | A | PASS |
|
|
Requesting a wall inspection. Phone #: ###-#### Internet Inspection Request from: Dan Hardisty walls and hard lids only ok to cover
|