FIR08-00238
| INSP-Final Inspection | 5/6/2008 | 5/7/2008 | 5/8/2008 10:32:10 AM | P | PART |
|
|
Final pending accurate riser diagram for field changes in circut connections and modified plans indicating omission of work shown for the conference room area not to be completed at this time per contractor. Functional testing for the K-9 office and kennel room alarm notification devices passed.
|
BLD08-00206
| FIRE-Final Inspection | 5/7/2008 | 5/7/2008 | 5/7/2008 3:10:25 PM | P | PASS |
|
|
C/N items verified, inspection passed.
|
BLD08-00342
| FIRE-Final Inspection | 5/7/2008 | 5/7/2008 | 5/7/2008 2:32:04 PM | P | FAIL |
|
|
Building modifications have disrupted existing fire sprinkler system coverage. A fire sprinkler permit will be required to complete the necessary corrections.
|
BLD08-00574
| FIRE-Final Inspection | 5/6/2008 | 5/7/2008 | 5/7/2008 1:54:23 PM | A | NH |
|
|
Door locked, no access to complete inspection.
|
BLD08-00573
| FIRE-Final Inspection | 5/6/2008 | 5/7/2008 | 5/7/2008 1:53:31 PM | A | PASS |
|
|
Items on correction notice are finished, life safety passed.
|
FIR08-00180
| INSP-Sprinkler Rough-in/Hydro | 5/6/2008 | 5/7/2008 | 5/7/2008 1:46:47 PM | A | PART |
|
|
OH install at the east office area first and second floors for rooms and areas completed to date are okay for cover, no access at one hallway due to flooring work underway, missing heads at two utility rooms 2nd floor, verified corrections are finished at the entry vestibule, need access to verify coverage at the concealed combustible spaces under the stairway at two locations. Hydrostatic testing for the new 10"supply main at the warehouse completed satisfactory, also discussed seismic bracing issues.
|