Inspections for the day of: Wednesday, May 7, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-02010 FIRE-Final Inspection5/7/20085/7/20085/7/2008 5:46:32 PMPPASS
Life safety passed
FIR08-00214 INSP-Sprinkler Rough-in/Hydro5/6/20085/7/20085/7/2008 3:55:42 PMPPART
The sprinkler rough-in for piping in the low areas is passed. The high area was not quite complete. The sprinkler piping can not be covered until the deck mounted insulation has been installed. I notified the fitter and the general contractor about a potential problem with the eaves qualifying as a combustible concealed space requireing protection.
FIR07-00248 INSP-Final Inspection5/7/20085/7/20085/7/2008 3:45:21 PMPPASS
permit finaled
BLD07-02253 FIRE-Final Inspection5/5/20085/7/20085/7/2008 3:44:49 PMAFAIL
The main entry/exit on the lower level still has the thumbturn installed and the indicator is missing. Also the fire extinguisher on the second level and the two exit signs on the second level still need repaired.
BLD07-02298 FIRE-Conference5/6/20085/7/20085/7/2008 1:39:57 PMAPASS
Life safety passed.
BLD07-01575 FIRE-Final Inspection5/7/20085/7/20085/7/2008 12:51:47 PMAPASS
Life safety passed.
BLD07-02078 FIRE-Final Inspection5/6/20085/7/20085/7/2008 12:38:32 PMAPASS
The life safety has already been passed.
BLD07-02706 FIRE-Final Inspection5/6/20085/7/20085/7/2008 12:38:02 PMAFAIL
The exit hardware on the second floor exit has not been installed yet and the bulbs are missing for the exterior stairway emergency lights. All other items are passed.
FIR08-00315 INSP-Final Inspection5/6/20085/7/20085/7/2008 11:12:58 AMAPASS
Permit finaled
BLD08-00284 FIRE-Final Inspection5/6/20085/7/20085/7/2008 10:04:42 AMAPASS
life safety passed
FIR08-00036 INSP-Sprinkler Rough-in/Hydro5/6/20085/7/20085/7/2008 9:09:55 AMAPART
24 hour air test started at 8:30am with 45 psi on the guage.