Inspections for the day of: Monday, May 7, 2012.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-01009 FIRE-Final Inspection5/7/20125/7/20125/7/2012 3:58:21 PMPFAIL
Provide single action hardware on the north exit door. Provide verification that the existing fire sprinkelr system is adequate for the commodity being stored. I found encapsulated foam mattresses stored (sollid pile) around 8'. Per the owner this is temporary and actual storage height will be at 4'.
FIR12-00216 INSP-Sprinkler Rough-in/Hydro5/7/20125/7/20125/7/2012 3:48:07 PMPPASS
Hydro test passed and pendant head has been relocated. Still need annual inspection for the fire sprinkler system.
FIR11-00574 INSP-Final Inspection5/7/20125/7/20125/7/2012 3:46:39 PMPPASS
Permit finaled
BLD12-00590 FIRE-Final Inspection5/7/20125/7/20125/7/2012 2:29:08 PMPPASS
life safety passed
BLD12-00587 FIRE-Final Inspection5/7/20125/7/20125/7/2012 2:28:14 PMPPASS
life safety passed
BLD11-01032 FIRE-Final Inspection5/4/20125/7/20125/7/2012 1:04:25 PMAFAIL
Provide remote annunciation per IMC 606.4.1. And then provide functional testing for sutdown verification.
FIR10-00469 INSP-Sprinkler Rough-in/Hydro5/4/20125/7/20125/7/2012 12:38:18 PMAFAIL
Testing is complete. Need as-builts showing the lack of trouble output and NFPA 72 record of completion forms.
BLD12-01028 FIRE-Final Inspection5/4/20125/7/20125/7/2012 11:08:37 AMAFAIL
Repair/test all of the exit signs and emergency lights. None of the test buttons functioned. Provide one 2A,10BC fire extinguisher with current inspection tag and mount as discussed. Remove the dead bolt lock from the massage room door.
BLD12-00970 FIRE-Final Inspection5/4/20125/7/20125/7/2012 10:51:46 AMAPASS
Life safety passed
FIR12-00207 INSP-Conference5/4/20125/7/20125/7/2012 8:11:25 AMACANC
My contact, dave, was sick so he had Mark Scharfen contact me about scheduling. Inspection to be canceled due to the remote annunciator not being installed. Mark asked about relocating it but I deferred him to Scott Arellano and the fire alarm plans examiner for approval.