ELE14-01153
| Temporary Service | 5/7/2014 | 5/7/2014 | 5/8/2014 10:45:11 AM | P | FAIL |
|
|
over head temp pole Phone #: ###-#### >> Inspection requested via web by Stephen Kren 240.24- over current devices shall be located below 6'7". 250.53(G)- Rod shall be installed so that at least 8' is in contact with soil. Idaho power requires meter height between 3' and 6'.
|
ELE14-00142
| Electrical Rough-In | 5/7/2014 | 5/7/2014 | 5/7/2014 4:08:28 PM | P | PASS |
|
|
joel - as early as possible please Phone #: ###-#### Upstairs kitchenette wall rough in ok cover
|
ELE14-00791
| Permanent Service | 5/7/2014 | 5/7/2014 | 5/7/2014 3:39:47 PM | P | PASS |
|
|
Service inspection at Western Aircraft infill building. Contact is Nate Cornell. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery Check for bushings of conduit containing conductor larger than #4 next trip. Service rough in ok
|
ELE14-00860
| Electrical Rough-In | 5/7/2014 | 5/7/2014 | 5/7/2014 3:03:33 PM | P | PASS |
|
|
grid ceiling by walk in cooler Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Ceiling grid by walk in cooler rough in ok cover
|
ELE13-02949
| Electrical Rough-In | 5/7/2014 | 5/7/2014 | 5/7/2014 2:51:32 PM | P | PASS |
|
|
Need pole light base inspection Phone #: ###-#### >> Inspection requested via web by Alan Lusk pole bases rough in ok cover
|
ELE14-00126
| Final | 5/6/2014 | 5/7/2014 | 5/7/2014 2:24:31 PM | P | PASS |
|
|
Jake Phone #: ###-#### Final ok
|
MIS14-00097
| ELE-Conference | 5/6/2014 | 5/7/2014 | 5/7/2014 10:42:50 AM | A | DONE |
|
|
complaint doing work without permit; remodel inside including elec, plm, mech. Changed utility room into bathroom and moved utility room to basement, kitchen remodel changed flat ceiling to vaulted ceiliing. Electrical concerns with grounding/safety. Elecgtrical contractor to go through house, secure permit, install proper devices on ungrounded circuits, install tamper resistant recepticals wher changed on grounded circuits, install spark rings where needed, install peninsula receptical, GFCI kitchen counter recepticals, remove flexible cord behind fireplace up high, and check for 15 amp wire install on 20 amp breaker for kitchen lighting
|
ELE14-00729
| Final | 5/7/2014 | 5/7/2014 | 5/7/2014 9:48:31 AM | A | NR |
|
|
Phone #: ###-#### >> Inspection requested via web by John VanZandt Siders removed out lights on addition. connot final do to open boxes
|
ELE14-01085
| Electrical Rough-In | 5/7/2014 | 5/7/2014 | 5/7/2014 9:24:44 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Jesse Fuentes Wiring to out lights. Rest to be ran under deck or surface mounted. Rough in ok cover
|
ELE13-02057
| Electrical Rough-In | 5/6/2014 | 5/7/2014 | 5/7/2014 8:55:42 AM | A | PASS |
|
|
Robert. 1st floor high ceiling. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy 2nd floor cans as noted on print and 6th floor CCD11 hard lid rough in ok cover
|