Inspections for the day of: Wednesday, May 7, 2014.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00299 INSP-Final Inspection5/7/20145/7/20145/7/2014 4:51:52 PMPPASS
Fire alarm permit finaled.
FIR12-00302 INSP-Final Inspection5/7/20145/7/20145/7/2014 4:51:05 PMPPASS
Fire alarm permit finaled.
BLD14-00573 FIRE-Sprinkler Rough-in5/7/20145/7/20145/7/2014 4:49:52 PMPPART
Okay to cover overhead fire sprinkler work at the grid ceilings.
BLD14-00571 FIRE-Conference5/7/20145/7/20145/7/2014 2:00:24 PMPDONE
Regarding project schedule, remodel work, elevator lobby fire phone jacks, etc.
BLD13-01666 FIRE-Final Inspection5/2/20145/7/20145/7/2014 11:30:09 AMAFAIL
C/N items include; remove keyed locking deadbolts above panic hardware at two locations including the north office area and south breakroom exit doors, post "door to remain...." signage at the main entry/exit, missing fire sprinkler coverage at the fire riser room, need to complete acceptance testing for the building related fire alarm permit work, post signage at the paint booth per fire code review notes.
FIR14-00216 INSP-Final Inspection5/6/20145/7/20145/7/2014 12:00:00 AMACANC
please call 30min ahead - charles Phone #: ###-####
BLD14-00989 FIRE-Final Inspection5/6/20145/7/20145/6/2014 4:30:10 PMAPASS
Inspection completed 5/6. Need to re-post address numbers and "door to remain....." signage when sanding/painting is finished and prior to structural final inspection as discussed.