Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01561 Conference5/7/20195/7/20195/7/2019 11:33:58 AMPDONE
Additional contact - Bryan Atkins ###-#### Phone #: ###-#### Inspection requested via web by Bryan Atkins
Discussed work being performed. Removing 6 flag poles and relocating conduits and circuits to festoon lighting and planter receptacles. Will verify all on final.
ELE19-01658 Rough-In Permanent Service5/6/20195/7/20195/7/2019 11:12:48 AMAPASS
This is a Century Link phone equipment site and this new power pedestal is a few feet northeast of the existing pet pedestal that it will be replacing. Phone #: ###-#### Inspection requested via web by Jeremiah Mitchell
Cabinet and underground rough in ok cover
p/s u/g n ok
ELE18-03866 Permanent Service5/6/20195/7/20195/7/2019 10:53:21 AMAFAIL
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
110.24- Available fault current shall be posted prior to permanent service inspection.
250.64- Grounding electrode conductor shall terminate at same location as grounded conductor or other location provided by manufacturer.
ELE19-01592 Rough-In Permanent Service5/6/20195/7/20195/7/2019 10:29:07 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kevin Heideman
300.14- A minimum of 6" of free conductor length shall be provided from where conductor emerges from sheath for splicing. Several found, check all and provide.
314.25- Recessed can junction box covers shall be installed to totally enclose opening on junction box. 3 found, 1 in kitchen, 1 in master bathroom, 1 in west hall.
334.30- Nm cable shall be secured with in 12" of a box. West hall desk area.
ELE19-01654 Rough-In Permanent Service5/6/20195/7/20195/7/2019 9:30:50 AMAPASS
Phone #: ###-#### Inspection requested via web by Mike Okamura
Service is energized at time of inspection. Chassis bond ok, underground and skirt rough in ok cover. p/s u/g rec ok
ELE19-00777 Final5/6/20195/7/20195/7/2019 9:29:18 AMAPASS
garage code 3484 Phone #: ###-#### Inspection requested via web by Neal Rumsey
Final ok