FIR19-00067 INSP-Supply line flush5/6/20195/7/20195/7/2019 12:00:00 AMAPASS
Performed underground flush. Passed inspection.

The contact is Colton Cox. Stacey with Suez is aware of this inspection, but please call him prior to when the inspector will be out there so Stacey can meet him there. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR18-00815 INSP-Final Inspection5/6/20195/7/20195/7/2019 12:00:00 AMAFAIL
Gym speaker circuit was not working (disabled in programming per dirk). Unable to get HVAC units running for testing shutdown. Asbuilds do not match what is installed. Gym has 115CD strobes but prints and load sheets show 110CD. Current rating doesn't match cut sheet for alarm current draw. Plans will need to be submitted as a plan mod prior to next inspection. Next inspection will have a reinspection fee.

Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten
BLD19-00419 FIRE-Final Inspection5/7/20195/7/20195/7/2019 12:00:00 AMPPASS
Paula Phone #: ###-####
BLD19-00130 FIRE-Final Inspection5/7/20195/7/20195/7/2019 12:00:00 AMPPASS
Passed fire life safety. Noticed that on deli next door exit door is now blocked by sidewalk cafe. Called GC who will remove exit sign from door (rear exit meets 2nd exit) and let Dave Hannah know via voice mail.