Inspections for the day of: Monday, May 8, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01319 Electrical Rough-In5/8/20065/8/20065/9/2006 7:28:18 AMPFAIL
For cover of inerior. I am told the cans are approved.; Phone #: ###-#### Internet Inspection Request from: Justin Yount
corr called 314.16 ,314.43, 314.20 outside boxes shall be flush at time of r/i, recess fixtures shall meet energy code and be labeled air tight
ELE06-01523 Permanent Service5/8/20065/8/20065/8/2006 4:25:54 PMPPASS
###-#### - tyler p/s o/h rec. ok
ELE06-01568 Electrical Rough-In5/8/20065/8/20065/8/2006 3:37:29 PMPPART
Phone #: ###-#### Internet Inspection Request from: Dana Moyer u/g ok corr. posted caled 110.26(F)(2) remove phone junk from below p/s, art. 500 group D gas needs rigid and sealoff for pump power and sensors cords
ELE05-02819 Electrical Rough-In5/8/20065/8/20065/8/2006 2:43:57 PMPFAIL
JAMES; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
corr. met owner pvc not large enough for wire fill, 300.5T needs 18" deep,, 314.28(A)(3) LB not big enough, 300.4(A)1)&(D) nail plates and 11/4" 334.30,314.17(B) secure nmb and mc within 12" of boxes , 250.53(G) drive grd rods as code states,,352.48 use approved cement for pvc, 250.64(C) no splices in GEC, note complete all wiring and makeup before inspection requested note partial correction only job not ready, told owner if more violations created permit could be voided
ELE06-01525 Permanent Service5/5/20065/8/20065/8/2006 1:47:28 PMPPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
p/s u/g rec. ok
ELE06-01525 Electrical Rough-In5/8/20065/8/20065/8/2006 1:47:01 PMPPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Barbara Moore r/i ok
ELE06-01553 Electrical Rough-In5/8/20065/8/20065/8/2006 1:09:58 PMPPART
RUMMER floor heat r/i ok for north unit only
ELE06-01593 Electrical Rough-In5/8/20065/8/20065/8/2006 12:33:35 PMPFAIL
Can you call me about an hour before due to I have the access into the house. Thank you; Phone #: ###-#### Internet Inspection Request from: Robert Murray corr. met contr. 314.43 no screws in plastic boxes, 314.16 box fill, 334.30/314.17(C) staple romex 8" of boxes, 300.4(A)(1)&(D) nail plates and 11/4", 210.52(B) no lights on SABC
ELE05-04573 Final5/5/20065/8/20065/8/2006 10:03:31 AMANR
rick; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called inspection ok needs access to j tub
ELE06-00446 Final5/5/20065/8/20065/8/2006 9:25:40 AMAFAIL
Internet Inspection Request from: Melyne Davis needs to update permit for correct number of rooms called
ELE06-00597 Final5/4/20065/8/20065/8/2006 9:21:53 AMAFAIL
Internet Inspection Request from: Melyne Davis permit needs to be updated for correct room count, and house done on t/s permit called
ELE05-03766 Final5/5/20065/8/20065/8/2006 9:20:38 AMAPASS
Internet Inspection Request from: Melyne Davis this is the permit for t/s not house
ELE06-00685 Final5/5/20065/8/20065/8/2006 9:19:44 AMAFAIL
Internet Inspection Request from: Melyne Davis house checked out needs to update permit for 15 rooms called
ELE06-00444 Final5/4/20065/8/20065/8/2006 9:18:20 AMANH
Internet Inspection Request from: Melyne Davis notice posted called also needs to update permit for correct room count
ELE05-03685 ELE-Aging Inspection5/8/20065/8/20065/8/2006 8:07:12 AM DONE
ELE05-03685 Final5/8/20065/8/20065/8/2006 8:06:57 AMAPASS
old sign new faces
ELE06-01568 Final5/8/20065/8/20065/8/2006 7:57:32 AMPCANC
Phone #: ###-#### Internet Inspection Request from: Dana Moyer Inspection cancelled from web by: Dana Moyer