FIR05-00864
| INSP-Sprinkler Rough-in | 5/5/2006 | 5/8/2006 | 5/9/2006 11:36:54 AM | A | PART |
|
|
Hangers at various locations are missing retaining straps at beam clamps, several hangers for arm-overs have been attatched to 5/8 sheetrock as a means of support-need to verify the point of attatchment will support a min. 250lbs per NFPA 13.
|
FIR05-00865
| INSP-Final Inspection | 5/5/2006 | 5/8/2006 | 5/9/2006 11:32:44 AM | A | PASS |
|
|
Corrections have been verified, fire alarm permit passed inspection.
|
BLD05-01216
| FIRE-Conference | 5/5/2006 | 5/8/2006 | 5/8/2006 4:37:35 PM | P | DONE |
|
|
Confrence to discuss requirements related to duct smoke detection for HVAC unit shutdown.
|
FIR06-00268
| INSP-Final Inspection | 5/8/2006 | 5/8/2006 | 5/8/2006 4:12:18 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD06-00094
| FIRE-Final Inspection | 5/8/2006 | 5/8/2006 | 5/8/2006 4:10:27 PM | P | PASS |
|
|
Fire life safety passed final inspection, project related alarm and sprinkler permits are finaled.
|
BLD06-00964
| FIRE-Sprinkler Rough-in | 5/8/2006 | 5/8/2006 | 5/8/2006 4:09:24 PM | P | FAIL |
|
|
The combination exit sign/emergency light at the main exit is non-functional on battery backup, all other items are okay. Need to final alarm permit (pending resubmittals) as well.
|
FIR06-00261
| INSP-Final Inspection | 5/5/2006 | 5/8/2006 | 5/8/2006 11:48:02 AM | A | PASS |
|
|
Overhead fire sprinkler work is satisfactory, required corrections have been made, inspection passed.
|
BLD05-02482
| FIRE-Final Inspection | 5/5/2006 | 5/8/2006 | 5/8/2006 11:10:24 AM | A | FAIL |
|
|
Need to provide a fire extinguisher with current tag for the basement, repair the exit sign 2nd floor stairs, provide permanent address numbers, missing door and hardware at the patio enclosure exit.
|
FIR06-00296
| INSP-Sprinkler Rough-in | 5/5/2006 | 5/8/2006 | 5/8/2006 10:39:46 AM | A | PART |
|
|
Rough-in is good for cover at the restroom and counter soffit hard lid areas only, noted one head is overspaced at the drop ceiling area as marked on approved plans, not all drop ceiling areas are ready for inspection at this time, will require matching response type heads in the same fire area.
|
BLD06-00325
| FIRE-Final Inspection | 5/5/2006 | 5/8/2006 | 5/8/2006 10:35:49 AM | A | PASS |
|
|
Corrections are completed, fire life safety passed inspection.
|