Inspections for the day of: Monday, May 8, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00864 INSP-Sprinkler Rough-in5/5/20065/8/20065/9/2006 11:36:54 AMAPART
Hangers at various locations are missing retaining straps at beam clamps, several hangers for arm-overs have been attatched to 5/8 sheetrock as a means of support-need to verify the point of attatchment will support a min. 250lbs per NFPA 13.
FIR05-00865 INSP-Final Inspection5/5/20065/8/20065/9/2006 11:32:44 AMAPASS
Corrections have been verified, fire alarm permit passed inspection.
BLD05-01216 FIRE-Conference5/5/20065/8/20065/8/2006 4:37:35 PMPDONE
Confrence to discuss requirements related to duct smoke detection for HVAC unit shutdown.
FIR06-00268 INSP-Final Inspection5/8/20065/8/20065/8/2006 4:12:18 PMPPASS
Fire sprinkler permit finaled.
BLD06-00094 FIRE-Final Inspection5/8/20065/8/20065/8/2006 4:10:27 PMPPASS
Fire life safety passed final inspection, project related alarm and sprinkler permits are finaled.
BLD06-00964 FIRE-Sprinkler Rough-in5/8/20065/8/20065/8/2006 4:09:24 PMPFAIL
The combination exit sign/emergency light at the main exit is non-functional on battery backup, all other items are okay. Need to final alarm permit (pending resubmittals) as well.
FIR06-00261 INSP-Final Inspection5/5/20065/8/20065/8/2006 11:48:02 AMAPASS
Overhead fire sprinkler work is satisfactory, required corrections have been made, inspection passed.
BLD05-02482 FIRE-Final Inspection5/5/20065/8/20065/8/2006 11:10:24 AMAFAIL
Need to provide a fire extinguisher with current tag for the basement, repair the exit sign 2nd floor stairs, provide permanent address numbers, missing door and hardware at the patio enclosure exit.
FIR06-00296 INSP-Sprinkler Rough-in5/5/20065/8/20065/8/2006 10:39:46 AMAPART
Rough-in is good for cover at the restroom and counter soffit hard lid areas only, noted one head is overspaced at the drop ceiling area as marked on approved plans, not all drop ceiling areas are ready for inspection at this time, will require matching response type heads in the same fire area.
BLD06-00325 FIRE-Final Inspection5/5/20065/8/20065/8/2006 10:35:49 AMAPASS
Corrections are completed, fire life safety passed inspection.