Inspections for the day of: Monday, May 8, 2006.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00223 INSP-Sprinkler Rough-in5/5/20065/8/20065/8/2006 3:53:51 PMPPART
Sprinkler piping is ok to cover except for the dining room area due to the pendant being overspaced and not tented. Per Bill plans need to be resubmitted showing the six added pendants, the corrected underground supply and the correct backflow preventor.
MIS06-00075 FIR-Final5/8/20065/8/20065/8/2006 3:50:44 PMPPART
A temporary occupancy was given until approved hardware is installed on the exterior exit doors, provide fire extinguishers front and rear, provide correct landing at the north exit door and cover all electrical outlets.
BLD05-03484 FIRE-Final Inspection5/5/20065/8/20065/8/2006 3:21:39 PMAFAIL
Provide sensors as per approval notes
BLD06-00690 FIRE-Sprinkler Rough-in5/5/20065/8/20065/8/2006 3:18:17 PMACANC
Contractor wanted an inspector to walk the project and tell them if any sprinkler heads are overspaced. I told him that I could not do this and that he would need to contact a fire sprinkler contractor to verify sprinkler spacing prior to inspection
BLD06-00834 FIRE-Final Inspection5/8/20065/8/20065/8/2006 1:20:17 PMPPASS
Life safety finaled
FIR06-00290 INSP-Sprinkler Rough-in5/5/20065/8/20065/8/2006 10:22:40 AMAFAIL
Per the plans the Server Room is to be Ordinary Hazard. The small room rule has been utilized plus the square footage of the room exceeds the coverage of what two heads could provide at 130sq ft each. The plans also indicate that the new pendants in the other room are to have a maximum spacing of 168 sq. ft. but are actually spaced at 183 sq. ft.. Also one sprig up has been left installed above what is going to be a ceiling. This upright will need to be removed.
FIR06-00223 INSP-Final Inspection5/5/20065/8/20065/5/2006 3:00:57 PMPCANC
James is the contact at ###-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice