ELE07-01652
| Conference | 5/8/2007 | 5/8/2007 | 5/8/2007 3:40:26 PM | A | DONE |
|
|
kevin ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
ELE07-01650
| Conference | 5/8/2007 | 5/8/2007 | 5/8/2007 3:39:24 PM | A | DONE |
|
|
met contr, wrote corr notice to owner saidBCC no violations shall be retained, example: emt, pvs, mc shall be strapped per code, no openings in boxes, boxes shall be mounted, electrical panel not in bathroom, mc shall be hospital grade with redundand grounding in x-ray room, metal boxes shall be grounded, plans shall be complete, u/g shall be under slab, maintain 1 1/4" for holes and cable and pvc
|
ELE07-00321
| Final | 5/8/2007 | 5/8/2007 | 5/8/2007 3:33:33 PM | P | PART |
|
|
ted; Phone #: ###-#### Internet Inspection Request from: Victoria called contr to put faceplates on in kitchen and do panel schedule then call for final
|
ELE07-00590
| Final | 5/8/2007 | 5/8/2007 | 5/8/2007 3:02:49 PM | P | PASS |
|
|
robert ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
|
ELE07-00590
| Permanent Service | 5/8/2007 | 5/8/2007 | 5/8/2007 3:01:16 PM | P | PASS |
|
|
robert ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corrections made, p/s o/h n ok
|
ELE07-01652
| Temporary Service | 5/8/2007 | 5/8/2007 | 5/8/2007 2:21:05 PM | P | FAIL |
|
|
kevin ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left corr notice, nec 250.24(A) gec shall be connected to grounded conductor at service, 312.5 all conductors entering enclosures shall have abrasion protection
|
ELE07-01648
| Permanent Service | 5/8/2007 | 5/8/2007 | 5/8/2007 1:49:44 PM | P | PASS |
|
|
brent; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left survey, nec 348.30 fmc shall be supported by an approved method within 12" of boxes
|
ELE07-01638
| Conference | 5/7/2007 | 5/8/2007 | 5/8/2007 1:30:55 PM | P | DONE |
|
|
kaj -- ###-#### call 1st before insp talked with owner about re-modek for house and when to call for inspection, how far to go to bring up to code, small appliance branch ckts, bath and outside ckts, range and dryer 4-wire
|
ELE07-00570
| Conference | 5/7/2007 | 5/8/2007 | 5/8/2007 12:40:47 PM | P | DONE |
|
|
gayla; Phone #: ###-#### Internet Inspection Request from: Victoria Beall reviewed fittings, 1 1/4", make-up, flush boxes, 6" free conductor, 15a gfci to feed garage
|
ELE07-01650
| Electrical Rough-In | 5/8/2007 | 5/8/2007 | 5/8/2007 10:32:50 AM | P | CANC |
|
|
dene - call for key location; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see conference
|
ELE07-01633
| Electrical Rough-In | 5/7/2007 | 5/8/2007 | 5/8/2007 9:46:37 AM | A | PASS |
|
|
jay; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ric ok
|
ELE07-01551
| Electrical Rough-In | 5/7/2007 | 5/8/2007 | 5/8/2007 8:59:36 AM | A | CANC |
|
|
joe - nursury bathroom; Phone #: ###-#### Internet Inspection Request from: Victoria Beall contr called wrong location for inspection
|
ELE07-01634
| Rough-In Permanent Service | 5/7/2007 | 5/8/2007 | 5/8/2007 8:46:35 AM | A | PASS |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ric ok, p/s u/g n ok
|
ELE07-01513
| Electrical Rough-In | 5/7/2007 | 5/8/2007 | 5/8/2007 8:08:30 AM | A | FAIL |
|
|
greg - underground pipe ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message, BCC all u/g shall be inspected before cover. (Raceway from bldg to sign at sw corner property) told bldr needed grade line to be sure 24" depth could be measured.
|
ELE07-01623
| Final | 5/7/2007 | 5/8/2007 | 5/7/2007 3:34:44 PM | A | PASS |
|
|
gayle ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see final
|