BLD07-03012
| FIRE-Final Inspection | 5/8/2008 | 5/8/2008 | 5/9/2008 11:46:44 AM | P | PASS |
|
|
Fire life safety finaled.
|
FIR07-00933
| INSP-Final Inspection | 5/7/2008 | 5/8/2008 | 5/9/2008 10:39:32 AM | P | FAIL |
|
|
Three wall post tampers at the main riser manifold need to be wired in the normally open condition, flow switch at riser #1 is out of adjustment, provide a map at the FACP per review note #10, descriptor at the west floor shop WP is not accurate. Remainder of fire alarm work passed testing.
|
BLD07-02423
| FIRE-Final Inspection | 5/8/2008 | 5/8/2008 | 5/8/2008 10:49:17 AM | P | NR |
|
|
Not ready at this time per phone call from contractor, to be rescheduled as discussed.
|
BLD08-00574
| FIRE-Final Inspection | 5/8/2008 | 5/8/2008 | 5/8/2008 10:48:12 AM | P | PASS |
|
|
Final okay per J. Storey and S. Zahorka.
|
FIR08-00129
| INSP-Final Inspection | 5/7/2008 | 5/8/2008 | 5/8/2008 10:45:02 AM | A | PART |
|
|
New duct detectors retested okay, verified as-built plans provided, missing updated map at the FACP per review note #7, noted different alarm contractor on site in process of relocating the remote annunciator and horn appliance under a separate permit- will verify map and test remainder of inputs from the two risers and clean agent system on the river street side when project related alarm work is also complete.
|