Inspections for the day of: Thursday, May 8, 2008.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-03012 FIRE-Final Inspection5/8/20085/8/20085/9/2008 11:46:44 AMPPASS
Fire life safety finaled.
FIR07-00933 INSP-Final Inspection5/7/20085/8/20085/9/2008 10:39:32 AMPFAIL
Three wall post tampers at the main riser manifold need to be wired in the normally open condition, flow switch at riser #1 is out of adjustment, provide a map at the FACP per review note #10, descriptor at the west floor shop WP is not accurate. Remainder of fire alarm work passed testing.
BLD07-02423 FIRE-Final Inspection5/8/20085/8/20085/8/2008 10:49:17 AMPNR
Not ready at this time per phone call from contractor, to be rescheduled as discussed.
BLD08-00574 FIRE-Final Inspection5/8/20085/8/20085/8/2008 10:48:12 AMPPASS
Final okay per J. Storey and S. Zahorka.
FIR08-00129 INSP-Final Inspection5/7/20085/8/20085/8/2008 10:45:02 AMAPART
New duct detectors retested okay, verified as-built plans provided, missing updated map at the FACP per review note #7, noted different alarm contractor on site in process of relocating the remote annunciator and horn appliance under a separate permit- will verify map and test remainder of inputs from the two risers and clean agent system on the river street side when project related alarm work is also complete.