FIR08-00214
| INSP-Sprinkler Rough-in/Hydro | 5/7/2008 | 5/8/2008 | 5/8/2008 4:06:50 PM | P | PASS |
|
|
The upper level piping rough-in is passed.
|
FIR08-00285
| INSP-Sprinkler Rough-in/Hydro | 5/6/2008 | 5/8/2008 | 5/8/2008 3:47:08 PM | A | PART |
|
|
The sprinkler rough-in as per the plans has passed with one exception. One additional upright sprinkler is required to continue protection behind a new wall where the existing upright sprinkler head is spaced too far away. This location has been marked on the city approved plans.
|
FIR08-00222
| INSP-Sprinkler Rough-in/Hydro | 5/7/2008 | 5/8/2008 | 5/8/2008 3:43:38 PM | A | PASS |
|
|
UG Cover Inspection passed. The underground piping as installed does not match the quick permit plan. The two 8" 45's have been removed and the underground now is run straight from the street to the riser room with no direction changes. I markded the permit plans and signed and dated them.
|
BLD06-01538
| FIRE-Final Inspection | 5/7/2008 | 5/8/2008 | 5/8/2008 11:02:32 AM | A | PASS |
|
|
fire life safety passed. There was no card on site to sign.
|
BLD07-02706
| FIRE-Final Inspection | 5/7/2008 | 5/8/2008 | 5/8/2008 9:56:10 AM | A | PASS |
|
|
fire life safety passed
|
FIR08-00036
| INSP-Sprinkler Rough-in/Hydro | 5/7/2008 | 5/8/2008 | 5/8/2008 9:41:17 AM | A | PASS |
|
|
24 hour air test passed
|