Inspections for the day of: Thursday, May 8, 2008.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00214 INSP-Sprinkler Rough-in/Hydro5/7/20085/8/20085/8/2008 4:06:50 PMPPASS
The upper level piping rough-in is passed.
FIR08-00285 INSP-Sprinkler Rough-in/Hydro5/6/20085/8/20085/8/2008 3:47:08 PMAPART
The sprinkler rough-in as per the plans has passed with one exception. One additional upright sprinkler is required to continue protection behind a new wall where the existing upright sprinkler head is spaced too far away. This location has been marked on the city approved plans.
FIR08-00222 INSP-Sprinkler Rough-in/Hydro5/7/20085/8/20085/8/2008 3:43:38 PMAPASS
UG Cover Inspection passed. The underground piping as installed does not match the quick permit plan. The two 8" 45's have been removed and the underground now is run straight from the street to the riser room with no direction changes. I markded the permit plans and signed and dated them.
BLD06-01538 FIRE-Final Inspection5/7/20085/8/20085/8/2008 11:02:32 AMAPASS
fire life safety passed. There was no card on site to sign.
BLD07-02706 FIRE-Final Inspection5/7/20085/8/20085/8/2008 9:56:10 AMAPASS
fire life safety passed
FIR08-00036 INSP-Sprinkler Rough-in/Hydro5/7/20085/8/20085/8/2008 9:41:17 AMAPASS
24 hour air test passed