GCE14-00065
| GCE-Rough-In Permanent Service | 5/8/2014 | 5/8/2014 | 5/8/2014 3:22:16 PM | P | PASS |
|
|
Daniel ###-#### rough-in p/s u/g n ok
|
GCE14-00058
| GCE-Temporary Service | 5/8/2014 | 5/8/2014 | 5/8/2014 2:46:49 PM | P | PASS |
|
|
Daniel ###-#### t/s u/g n ok
|
ELE14-01169
| Rough-In Permanent Service | 5/8/2014 | 5/8/2014 | 5/8/2014 2:22:18 PM | P | NR |
|
|
Phone #: ###-#### >> Inspection requested via web by David Nelson Not ready for any cover
|
ELE14-01169
| Permanent Service | 5/8/2014 | 5/8/2014 | 5/8/2014 2:21:29 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by David Nelson p/s o/h rec ok
|
ELE14-01125
| Final | 5/8/2014 | 5/8/2014 | 5/8/2014 1:54:22 PM | P | PASS |
|
|
job complete, final ok
|
ELE14-01125
| Electrical Rough-In | 5/8/2014 | 5/8/2014 | 5/8/2014 1:52:53 PM | P | PASS |
|
|
Call half hour before I CAN meet you there .Thanks Phone #: ###-#### >> Inspection requested via web by mark hood Mobile home connection, contractor dug test holes to verify conduit depth. Rough-in ok
|
ELE14-01113
| Temporary Service | 5/8/2014 | 5/8/2014 | 5/8/2014 1:11:10 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Tracy Robertson t/s o/h n ok
|
ELE13-02849
| Electrical Rough-In | 5/8/2014 | 5/8/2014 | 5/8/2014 12:52:47 PM | P | PASS |
|
|
Contact is Alan Krishnek Phone #: ###-#### >> Inspection requested via web by Scott Campbell Rough-in ok cover phase 2 Lab and storage room
|
ELE13-02949
| Final | 5/8/2014 | 5/8/2014 | 5/8/2014 12:31:30 PM | P | PART |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk Partial final ok
|
ELE14-01155
| Permanent Service | 5/7/2014 | 5/8/2014 | 5/8/2014 11:17:28 AM | A | FAIL |
|
|
Brent Phone #: ###-#### NEC 110.26 Working clearance for service panel NEC 408.17 Location relative to easily ignitible material NEC 240.24(D)
|
GCE13-00208
| GCE-Rough-In Permanent Service | 5/7/2014 | 5/8/2014 | 5/8/2014 9:58:23 AM | A | PART |
|
|
(Mandatory Inspection) Would like a Rough-in to cover and a permanent service inspection. Walls in office area already onesided, Rough-in ok cover remainder of office area only. No riser room cover
|
GCE14-00046
| GCE-Final | 5/7/2014 | 5/8/2014 | 5/8/2014 9:11:55 AM | A | PASS |
|
|
Jeff ###-#### correction done final ok
|
ELE14-01166
| Electrical Rough-In | 5/7/2014 | 5/8/2014 | 5/8/2014 8:50:19 AM | A | PASS |
|
|
Phone #: 2088662787 >> Inspection requested via mobile web by Clay Jackson rough-in ok cover (House)
|
ELE14-01166
| Permanent Service | 5/8/2014 | 5/8/2014 | 5/8/2014 8:47:26 AM | A | PASS |
|
|
Phone #: 2088662787 >> Inspection requested via mobile web by Clay Jackson p/s u/g n ok
|
ELE14-00732
| Final | 5/7/2014 | 5/8/2014 | 5/7/2014 2:43:07 PM | A | PASS |
|
|
Final inspection. Please call Kyle ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate final ok
|