ELE17-01329
| Electrical Rough-In | 5/8/2017 | 5/8/2017 | 5/8/2017 3:17:16 PM | P | PASS |
|
|
Please call when on your way. I want to make sure someone is there. Thank you Phone #: ###-#### Inspection requested via web by Eric Brown Cans and switching fished in all rooms, heater in bath near shower shall be listed for damp location as per 424.12(B). Bath and kitchen areas rough in ok cover
|
ELE17-00624
| Final | 5/5/2017 | 5/8/2017 | 5/8/2017 2:31:10 PM | P | FAIL |
|
|
Jason is the contact his cell is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Building permit must be issued prior to final inspection. 210.8- All 15 and 20 amp 120 volt receptacle outlets located in the kitchen shall have GFCI protection.
|
ELE17-00769
| Final | 5/8/2017 | 5/8/2017 | 5/8/2017 2:22:18 PM | P | PASS |
|
|
Final Contact is Ken Williams ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves Attached to BLD16-04453. Final ok
|
ELE17-01336
| Electrical Rough-In | 5/8/2017 | 5/8/2017 | 5/8/2017 1:30:03 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan Wall rough in ok cover
|
ELE17-00037
| Final | 5/5/2017 | 5/8/2017 | 5/8/2017 12:48:17 PM | P | PASS |
|
|
Final Inspection on ADA Units 811 and 813 Contact Dan Hutchinson Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek All units done. Final ok
|
ELE13-01291
| Electrical Rough-In | 5/5/2017 | 5/8/2017 | 5/8/2017 11:18:29 AM | A | PASS |
|
|
Please inspect amphitheater wall #5. Please walk with Tony to sign off hard card on Simplot Headquarters past inspection. Phone #: ###-#### Inspection requested via web by Tom Betty Unable to sign on vanilla space under BLD16-03847. A seperate electrical permit required. Level 5 of ampitheater rough in ok cover.
|
ELE16-03480
| Permanent Service | 5/7/2017 | 5/8/2017 | 5/8/2017 9:53:39 AM | A | PASS |
|
|
If needed into home lock box is hanging on rail by front door code is 1978. Home is vacant. Phone #: ###-#### Inspection requested via web by Josh Craig p/s o/h n ok
|
ELE17-01355
| Rough-In Permanent Service | 5/5/2017 | 5/8/2017 | 5/8/2017 9:28:39 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk rough in ok cover p/s u/g n ok
|
ELE17-00902
| Final | 5/5/2017 | 5/8/2017 | 5/8/2017 8:31:59 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan Needed permenant service inspection. 110.3- Expansion joint shall be installed as per manufacturers instructions. Barrel opening to face down so not to collect dirt or water. 110.24- Available fault current shall be posted prior to permenant service inspection.
|
ELE14-01385
| Final | 5/8/2017 | 5/8/2017 | 5/8/2017 8:03:49 AM | P | PASS |
|
|
All temp power equipment rmoved. Final ok
|