Inspections for the day of: Monday, May 8, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01329 Electrical Rough-In5/8/20175/8/20175/8/2017 3:17:16 PMPPASS
Please call when on your way. I want to make sure someone is there. Thank you Phone #: ###-#### Inspection requested via web by Eric Brown
Cans and switching fished in all rooms, heater in bath near shower shall be listed for damp location as per 424.12(B). Bath and kitchen areas rough in ok cover
ELE17-00624 Final5/5/20175/8/20175/8/2017 2:31:10 PMPFAIL
Jason is the contact his cell is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
Building permit must be issued prior to final inspection.
210.8- All 15 and 20 amp 120 volt receptacle outlets located in the kitchen shall have GFCI protection.
ELE17-00769 Final5/8/20175/8/20175/8/2017 2:22:18 PMPPASS
Final
Contact is Ken Williams ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves
Attached to BLD16-04453. Final ok
ELE17-01336 Electrical Rough-In5/8/20175/8/20175/8/2017 1:30:03 PMPPASS
Phone #: ###-#### Inspection requested via web by steve ragan
Wall rough in ok cover
ELE17-00037 Final5/5/20175/8/20175/8/2017 12:48:17 PMPPASS
Final Inspection on ADA Units 811 and 813
Contact Dan Hutchinson
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
All units done. Final ok
ELE13-01291 Electrical Rough-In5/5/20175/8/20175/8/2017 11:18:29 AMAPASS
Please inspect amphitheater wall #5. Please walk with Tony to sign off hard card on Simplot Headquarters past inspection. Phone #: ###-#### Inspection requested via web by Tom Betty
Unable to sign on vanilla space under BLD16-03847. A seperate electrical permit required.
Level 5 of ampitheater rough in ok cover.
ELE16-03480 Permanent Service5/7/20175/8/20175/8/2017 9:53:39 AMAPASS
If needed into home lock box is hanging on rail by front door code is 1978. Home is vacant. Phone #: ###-#### Inspection requested via web by Josh Craig
p/s o/h n ok
ELE17-01355 Rough-In Permanent Service5/5/20175/8/20175/8/2017 9:28:39 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
rough in ok cover p/s u/g n ok
ELE17-00902 Final5/5/20175/8/20175/8/2017 8:31:59 AMAFAIL
Phone #: ###-#### Inspection requested via web by steve ragan
Needed permenant service inspection.
110.3- Expansion joint shall be installed as per manufacturers instructions. Barrel opening to face down so not to collect dirt or water.
110.24- Available fault current shall be posted prior to permenant service inspection.
ELE14-01385 Final5/8/20175/8/20175/8/2017 8:03:49 AMPPASS
All temp power equipment rmoved.
Final ok