BLD02-00843
| FIRE-Final Inspection | 5/8/2002 | 5/9/2002 | 5/9/2002 12:00:00 AM | A | FAIL |
|
|
duct detector that was installed is not listed for outdoor use. Contractor to supply listed enclosure and call for re-inspection 5/9/2002 11:11:31 AM
|
BLD01-02505
| FIRE-Final Inspection | 5/8/2002 | 5/9/2002 | 5/9/2002 12:00:00 AM | A | PASS |
|
|
fire sprinkler and fire life/safety finaled 5/9/2002 8:19:40 AM
|
BLD01-02964
| FIRE-Final Inspection | 5/8/2002 | 5/9/2002 | 5/9/2002 12:00:00 AM | A | PASS |
|
|
OK for perm occ 5/9/2002 10:02:07 AM
|
FIR02-00048
| INSP-Alarm Testing | 5/8/2002 | 5/9/2002 | 5/9/2002 12:00:00 AM | P | FAIL |
|
|
provide missing esch. for sprinkler pendants, remove dead bolt on south exit door, mount fire extinguishers at 48", provide signage for fire extinguishers, relocate knox box, provide building address 5/10/2002 8:47:20 AM
|
FIR02-00099
| INSP-Sprinkler Rough-in/Hydro | 5/9/2002 | 5/9/2002 | 5/9/2002 12:00:00 AM | P | CANC |
|
|
###-#### rick
|