Inspections for the day of: Friday, May 9, 2003.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00146 INSP-Sprinkler Rough-in/Hydro5/8/20035/9/20035/12/2003 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 5/8/2003 at 12:09:16 PM. Contact: ###-####. need head added in closet on main floor; tenting not ready; okay to cover walls and areas not requiring tenting 5/12/2003 10:09:14 AM
FIR03-00146 INSP-Supply line flush5/8/20035/9/20035/12/2003 12:00:00 AMPNR
Scheduled by a contractor via Hello! on 5/8/2003 at 12:10:08 PM. Contact: ###-####.
FIR03-00114 INSP-Final Inspection5/9/20035/9/20035/12/2003 12:00:00 AMPNH
Scheduled by a contractor via Hello! on 5/9/2003 at 10:36:49 AM. Contact: ###-####. OWNER NOT HOME 5/12/2003 8:56:23 AM
FIR03-00029 INSP-Final Inspection5/8/20035/9/20035/9/2003 12:00:00 AMAFAIL
###-#### robert Node 4 has ground fault; labels on several detectors not correct - see mapnet listing; strobes overspaced in mezzanine; nned to test dry sprinkler system and all troubles for TAC panels; need to test alarm condition for proper noise levels through speakers; need to drop test all overhead doors; ned to test troubles on main FACP; need programmed button labels on main FACP 5/9/2003 5:00:02 PM
BLD02-02663 FIRE-Final Inspection5/8/20035/9/20035/9/2003 12:00:00 AMAFAIL
richard; Phone #: ###-#### Internet Inspection Request from: Annette Moore emergency lights not working; need to test duct detectors for AHU shutdown (two new units on roof); extinguisher mounted too high and need current tag on northeast extinguisher 5/9/2003 4:46:41 PM
FIR03-00107 INSP-Final Inspection5/8/20035/9/20035/9/2003 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 5/8/2003 at 2:18:36 PM. Contact: ###-####. rescheduled for next week 5/12/2003 12:23:13 PM
FIR02-00228 INSP-Final Inspection5/5/20035/9/20035/8/2003 12:00:00 AMACANC
This is Grants Cell. Needs to be tested at 7:00 am if thats OK
Have a great day.; Phone #: ###-#### Internet Inspection Request from: Terry Owsley called Rob of Protex and told him I would not be able to do this inspection on 5/09 and he said he would reschedule for next week 5/8/2003 1:10:59 PM