ELE05-01580
| Temporary Service | 5/6/2005 | 5/9/2005 | 5/9/2005 12:00:00 AM | A | NR |
|
|
Temp Power Pole Inspection; Phone #: ###-#### Internet Inspection Request from: Casey Sells called contr, told not ready , ground not hooked up, fee due. 5/9/2005 8:19:14 AM
|
ELE04-03006
| Final | 5/9/2005 | 5/9/2005 | 5/9/2005 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 5/9/2005 at 7:16:16 AM. Contact: ###-####. west wall recpts for office dividers only. 5/9/2005 8:14:28 AM
|
ELE05-01583
| Electrical Rough-In | 5/6/2005 | 5/9/2005 | 5/9/2005 12:00:00 AM | A | PASS |
|
|
ANY QUESTIONS PLEASE CALL ED SCHALLOCK; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ric walls only ok 5/9/2005 9:07:45 AM
|
ELE05-01575
| Electrical Rough-In | 5/6/2005 | 5/9/2005 | 5/9/2005 12:00:00 AM | A | PASS |
|
|
dennis ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to cover wall only 5/9/2005 9:56:44 AM
|
ELE04-02595
| Final | 5/6/2005 | 5/9/2005 | 5/9/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 5/6/2005 at 2:54:50 PM. Contact: ###-####. 1st floor meeting rooms, offices, laundry, elect, phone rooms inspected. 110.26(A) work space about equipment shall be provided. 30" wide and 3'-0" minimum. 110.26(F)(1) no foreign equipment shall be in dedicated work zone 5/9/2005 1:21:08 PM
|
ELE05-00857
| Final | 5/6/2005 | 5/9/2005 | 5/9/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/6/2005 at 12:41:43 PM. Contact: ###-####. corrections made, ok to final 5/9/2005 4:15:51 PM
|
ELE05-00817
| Final | 5/9/2005 | 5/9/2005 | 5/9/2005 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/9/2005 at 7:55:32 AM. Contact: ###-####. ok to final 5/9/2005 4:18:41 PM
|
ELE05-01616
| Temporary Service | 5/9/2005 | 5/9/2005 | 5/9/2005 12:00:00 AM | P | PASS |
|
|
paul ###-#### t/s u/g n ok 5/9/2005 2:24:35 PM
|
ELE05-01614
| Rough-In Permanent Service | 5/9/2005 | 5/9/2005 | 5/9/2005 12:00:00 AM | P | PASS |
|
|
alan ###-#### ric ok, p/s u/g n ok 5/9/2005 12:08:34 PM
|
ELE05-01580
| Temporary Service | 5/9/2005 | 5/9/2005 | 5/9/2005 12:00:00 AM | P | PASS |
|
|
Ground Corrected, Re-Inspection for Power Pole; Phone #: ###-#### Internet Inspection Request from: Casey Sells finished, t/s u/g n ok 5/9/2005 1:53:32 PM
|