ELE05-00855
| ELE-Aging Inspection | 5/9/2006 | 5/9/2006 | 5/9/2006 4:31:59 PM | | DONE |
|
|
project suc
|
ELE06-00314
| Final | 5/9/2006 | 5/9/2006 | 5/9/2006 4:20:50 PM | P | PASS |
|
|
ready for final, please contact Tom Gilbert, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters called contr to strap rnc risers, ok to final
|
ELE06-01627
| Electrical Rough-In | 5/9/2006 | 5/9/2006 | 5/9/2006 3:56:21 PM | P | NR |
|
|
Upher Ground; Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton called contr, said there didn't appear to be 20' of copper in loop as laid out. He will recall with copper in straight line
|
ELE06-00404
| Final | 5/9/2006 | 5/9/2006 | 5/9/2006 3:31:48 PM | P | PASS |
|
|
looked at signs, ok to final
|
ELE06-01371
| Electrical Rough-In | 5/8/2006 | 5/9/2006 | 5/9/2006 3:10:12 PM | P | PASS |
|
|
###-#### kitchen and bath ric ok
|
ELE06-01619
| Electrical Rough-In | 5/8/2006 | 5/9/2006 | 5/9/2006 2:45:12 PM | P | PASS |
|
|
###-#### - rick ric ok
|
ELE06-01619
| Permanent Service | 5/9/2006 | 5/9/2006 | 5/9/2006 2:44:31 PM | P | PASS |
|
|
p/s u/g n ok
|
ELE05-04272
| ELE-Aging Inspection | 5/9/2006 | 5/9/2006 | 5/9/2006 2:30:08 PM | | DONE |
|
|
see final
|
ELE05-04272
| Final | 5/9/2006 | 5/9/2006 | 5/9/2006 2:29:48 PM | P | PASS |
|
|
called contr to put on box at end of nm cable with blank cover , ok to final
|
ELE06-00931
| Final | 5/9/2006 | 5/9/2006 | 5/9/2006 1:52:08 PM | P | PASS |
|
|
Internet Inspection Request from: Rowdy Monroe called contr, left survey, nec 422.16(B)(2) disposal cord shall be max 3' long
|
ELE06-00447
| Final | 5/8/2006 | 5/9/2006 | 5/9/2006 11:47:29 AM | A | PASS |
|
|
Please call if you have problems. Thanks; Phone #: ###-#### Internet Inspection Request from: Shane Vigil ok to final
|
ELE06-01538
| Rough-In Permanent Service | 5/8/2006 | 5/9/2006 | 5/9/2006 10:23:20 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/8/2006 at 3:17:41 PM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
|
ELE06-01404
| Rough-In Permanent Service | 5/8/2006 | 5/9/2006 | 5/9/2006 9:59:26 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 5/8/2006 at 1:38:36 PM. Contact: ###-####. ric ok, p/s u/g n ok
|
ELE06-01614
| Electrical Rough-In | 5/8/2006 | 5/9/2006 | 5/9/2006 9:09:37 AM | A | PART |
|
|
bill -###-#### all but south wall anop ok to cover walls only
|
ELE06-01615
| Temporary Service | 5/8/2006 | 5/9/2006 | 5/9/2006 8:37:52 AM | A | FAIL |
|
|
###-#### called contr, left corr notice 250.92(A)(2) the metal parts (gnd lug) shall be bonded to grounded term lug
|
ELE06-01612
| Electrical Rough-In | 5/8/2006 | 5/9/2006 | 5/9/2006 8:11:16 AM | A | PASS |
|
|
ufer ground ; Phone #: ###-#### Internet Inspection Request from: Jim Williams ok to pour u/g gec
|