FIR06-00862
| FIR-Aging Inspection | 5/9/2007 | 5/9/2007 | 5/10/2007 8:08:36 AM | | DONE |
|
|
wip, pending field inspection request.
|
FIR06-00864
| INSP-Final Inspection | 5/8/2007 | 5/9/2007 | 5/10/2007 8:05:33 AM | A | PASS |
|
|
Fire alarm testing completed satisfactory for the 2nd and 14th floors.
|
FIR07-00161
| INSP-Final Inspection | 5/9/2007 | 5/9/2007 | 5/10/2007 8:03:56 AM | P | PASS |
|
|
Hood suppression system operated correctly under test conditions, noted one appliance to be raised within the req 4' of edge of the hood and need to install missing cover plate at one demoed j-box.
|
FIR07-00306
| INSP-Sprinkler Rough-in | 5/9/2007 | 5/9/2007 | 5/10/2007 8:00:50 AM | P | PART |
|
|
c/n completed, OH fire sprinkler modifications are good for cover at the drop ceilings.
|
FIR07-00315
| INSP-Sprinkler Rough-in | 5/8/2007 | 5/9/2007 | 5/9/2007 1:34:51 PM | A | NR |
|
|
Work is not yet completed for inspection at this time.
|
FIR06-01010
| INSP-Sprinkler Rough-in | 5/8/2007 | 5/9/2007 | 5/9/2007 1:02:50 PM | A | PART |
|
|
OH hydrostatic testing for the basement system, standpipe, and FDC piping completed satisfactory.
|
BLD07-00907
| FIRE-Final Inspection | 5/8/2007 | 5/9/2007 | 5/9/2007 12:42:42 PM | A | PASS |
|
|
Fire life safety passed, notified contractor that automatic flush bolts at the inactive leaf on the main entry/exit pair of doors to be installed prior to structural final as agreed.
|
FIR07-00118
| INSP-Final Inspection | 5/8/2007 | 5/9/2007 | 5/9/2007 12:40:39 PM | A | PASS |
|
|
Fire alarm work passed field inspection, approved as-builts for the deletion of 3 non-required duct detectors, noted added strobe at one location, incorrect cd at one device changed while on site, also noted trouble at the panel for one sd on the 4th floor pending replacement per contractor.
|
FIR07-00292
| INSP-Final Inspection | 5/8/2007 | 5/9/2007 | 5/9/2007 12:36:34 PM | A | PASS |
|
|
Fire sprinkler final inspection passed, permit finaled.
|
BLD06-02498
| FIRE-Final Inspection | 5/8/2007 | 5/9/2007 | 5/9/2007 12:35:23 PM | A | FAIL |
|
|
Need certification tags for the provided fire extinguishers, post building address viewable from the street, provide signage at the main entry/exit doors.
|
FIR07-00306
| INSP-Sprinkler Rough-in | 5/8/2007 | 5/9/2007 | 5/9/2007 12:32:27 PM | A | FAIL |
|
|
Noted several beam clamp retaining straps not attatched to the structure, one hanger missing, locations noted on stamped plan set.
|