Inspections for the day of: Wednesday, May 9, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00862 FIR-Aging Inspection5/9/20075/9/20075/10/2007 8:08:36 AM DONE
wip, pending field inspection request.
FIR06-00864 INSP-Final Inspection5/8/20075/9/20075/10/2007 8:05:33 AMAPASS
Fire alarm testing completed satisfactory for the 2nd and 14th floors.
FIR07-00161 INSP-Final Inspection5/9/20075/9/20075/10/2007 8:03:56 AMPPASS
Hood suppression system operated correctly under test conditions, noted one appliance to be raised within the req 4' of edge of the hood and need to install missing cover plate at one demoed j-box.
FIR07-00306 INSP-Sprinkler Rough-in5/9/20075/9/20075/10/2007 8:00:50 AMPPART
c/n completed, OH fire sprinkler modifications are good for cover at the drop ceilings.
FIR07-00315 INSP-Sprinkler Rough-in5/8/20075/9/20075/9/2007 1:34:51 PMANR
Work is not yet completed for inspection at this time.
FIR06-01010 INSP-Sprinkler Rough-in5/8/20075/9/20075/9/2007 1:02:50 PMAPART
OH hydrostatic testing for the basement system, standpipe, and FDC piping completed satisfactory.
BLD07-00907 FIRE-Final Inspection5/8/20075/9/20075/9/2007 12:42:42 PMAPASS
Fire life safety passed, notified contractor that automatic flush bolts at the inactive leaf on the main entry/exit pair of doors to be installed prior to structural final as agreed.
FIR07-00118 INSP-Final Inspection5/8/20075/9/20075/9/2007 12:40:39 PMAPASS
Fire alarm work passed field inspection, approved as-builts for the deletion of 3 non-required duct detectors, noted added strobe at one location, incorrect cd at one device changed while on site, also noted trouble at the panel for one sd on the 4th floor pending replacement per contractor.
FIR07-00292 INSP-Final Inspection5/8/20075/9/20075/9/2007 12:36:34 PMAPASS
Fire sprinkler final inspection passed, permit finaled.
BLD06-02498 FIRE-Final Inspection5/8/20075/9/20075/9/2007 12:35:23 PMAFAIL
Need certification tags for the provided fire extinguishers, post building address viewable from the street, provide signage at the main entry/exit doors.
FIR07-00306 INSP-Sprinkler Rough-in5/8/20075/9/20075/9/2007 12:32:27 PMAFAIL
Noted several beam clamp retaining straps not attatched to the structure, one hanger missing, locations noted on stamped plan set.