Inspections for the day of: Friday, May 9, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00101 INSP-Final Inspection5/8/20085/9/20085/12/2008 11:51:18 AMADEFR
BLD08-00244 FIRE-Final Inspection5/9/20085/9/20085/12/2008 11:23:31 AMPPART
NOTE: Actual building address is 2563, address per permit documents is 2622.
FIR07-00606 INSP-Sprinkler Rough-in5/8/20085/9/20085/9/2008 4:59:20 PMAPART
Verification for beam clamp retaining strap attatchments at the first floor NW and SW classroom wings only, noted overspaced hangers at three locations SW wing.
FIR07-00663 INSP-Sprinkler Rough-in5/9/20085/9/20085/9/2008 4:56:13 PMPFAIL
UG fire supply line is not approved for cover due to missing meter installation per plan, depth of bury does not meet min. requirements adjacent to the foundation.
FIR08-00238 INSP-Final Inspection5/9/20085/9/20085/9/2008 11:46:13 AMPPASS
Contractor to provide requested documentation, finaled per building scope.
FIR08-00149 INSP-Final Inspection5/8/20085/9/20085/9/2008 11:44:32 AMAPASS
Fire sprinkler permit finaled, paper bags at heads in the kennel area to be removed prior to structural final as agreed.
FIR08-00247 INSP-Final Inspection5/7/20085/9/20085/9/2008 10:51:43 AMAPART
East office, open work room and conference room remodels indicated within the scope of work are not completed at this time, noted overspaced notification device at the SE open area, remainder of permit work tested acceptable, cd at one a/v in a conference room adjusted while on site.
FIR08-00297 INSP-Final Inspection5/7/20085/9/20085/9/2008 10:45:26 AMAPASS
Fire alarm field testing passed, one notification appliance re-attatched to the wall while on site, scope of permit work finaled.
FIR06-00782 INSP-Final Inspection5/7/20085/9/20085/9/2008 10:42:52 AMAPART
Phone #: ###-#### Internet Inspection Request from: John Warnick
FIR06-00615 INSP-Final Inspection5/7/20085/9/20085/9/2008 10:41:13 AMANR
Missing resubmittal plan set as necessary for permit final.
FIR08-00301 INSP-Sprinkler Rough-in5/8/20085/9/20085/9/2008 10:32:13 AMAPART
Ceilings at the womens and mens restroom and the custodial room are approved for cover, noted spacing issue at the open area adjacent to the removed partition, remainder of permit work is not yet completed.
FIR06-00615 INSP-Sprinkler Rough-in/Hydro5/7/20085/9/20085/7/2008 10:04:40 AMACANC
Phone #: ###-#### Internet Inspection Request from: John Warnick Inspection cancelled from web by: John Warnick