FIR08-00101
| INSP-Final Inspection | 5/8/2008 | 5/9/2008 | 5/12/2008 11:51:18 AM | A | DEFR |
|
|
|
BLD08-00244
| FIRE-Final Inspection | 5/9/2008 | 5/9/2008 | 5/12/2008 11:23:31 AM | P | PART |
|
|
NOTE: Actual building address is 2563, address per permit documents is 2622.
|
FIR07-00606
| INSP-Sprinkler Rough-in | 5/8/2008 | 5/9/2008 | 5/9/2008 4:59:20 PM | A | PART |
|
|
Verification for beam clamp retaining strap attatchments at the first floor NW and SW classroom wings only, noted overspaced hangers at three locations SW wing.
|
FIR07-00663
| INSP-Sprinkler Rough-in | 5/9/2008 | 5/9/2008 | 5/9/2008 4:56:13 PM | P | FAIL |
|
|
UG fire supply line is not approved for cover due to missing meter installation per plan, depth of bury does not meet min. requirements adjacent to the foundation.
|
FIR08-00238
| INSP-Final Inspection | 5/9/2008 | 5/9/2008 | 5/9/2008 11:46:13 AM | P | PASS |
|
|
Contractor to provide requested documentation, finaled per building scope.
|
FIR08-00149
| INSP-Final Inspection | 5/8/2008 | 5/9/2008 | 5/9/2008 11:44:32 AM | A | PASS |
|
|
Fire sprinkler permit finaled, paper bags at heads in the kennel area to be removed prior to structural final as agreed.
|
FIR08-00247
| INSP-Final Inspection | 5/7/2008 | 5/9/2008 | 5/9/2008 10:51:43 AM | A | PART |
|
|
East office, open work room and conference room remodels indicated within the scope of work are not completed at this time, noted overspaced notification device at the SE open area, remainder of permit work tested acceptable, cd at one a/v in a conference room adjusted while on site.
|
FIR08-00297
| INSP-Final Inspection | 5/7/2008 | 5/9/2008 | 5/9/2008 10:45:26 AM | A | PASS |
|
|
Fire alarm field testing passed, one notification appliance re-attatched to the wall while on site, scope of permit work finaled.
|
FIR06-00782
| INSP-Final Inspection | 5/7/2008 | 5/9/2008 | 5/9/2008 10:42:52 AM | A | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: John Warnick
|
FIR06-00615
| INSP-Final Inspection | 5/7/2008 | 5/9/2008 | 5/9/2008 10:41:13 AM | A | NR |
|
|
Missing resubmittal plan set as necessary for permit final.
|
FIR08-00301
| INSP-Sprinkler Rough-in | 5/8/2008 | 5/9/2008 | 5/9/2008 10:32:13 AM | A | PART |
|
|
Ceilings at the womens and mens restroom and the custodial room are approved for cover, noted spacing issue at the open area adjacent to the removed partition, remainder of permit work is not yet completed.
|
FIR06-00615
| INSP-Sprinkler Rough-in/Hydro | 5/7/2008 | 5/9/2008 | 5/7/2008 10:04:40 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: John Warnick Inspection cancelled from web by: John Warnick
|