Inspections for the day of: Friday, May 9, 2008.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00256 INSP-Sprinkler Rough-in5/8/20085/9/20085/9/2008 4:13:40 PMAPASS
The underground supply line was installed as per plan and can be covered. It took three trips to perfom this inspection due to the piping being covered with sand and no access into the trench to verify the pipe size installed.
FIR07-00874 INSP-Sprinkler Rough-in/Hydro5/7/20085/9/20085/9/2008 3:49:07 PMAPART
The hydro test of the south wing dry system passed. The hydro test of the south wing wet system failed.
BLD07-02423 FIRE-Final Inspection5/9/20085/9/20085/9/2008 2:24:54 PMAFAIL
Provide tags for the three fire extinguishers. Provide remote annunciators as discussed for the duct smoke detectors. The duct smoke detectors are mounted in the 90 degree elbows of the return air ducting. A manometer test will be required or the ducting modified to the 6 to 10 duct widths as per NFPA 72. All other items checked out ok.
FIR08-00212 INSP-Sprinkler Rough-in/Hydro5/8/20085/9/20085/9/2008 12:39:03 PMAFAIL
The approved plans that were on site the last inspection have disapeared. I let the fire sprinkler contractor know where to get copies. I went over the previous deficiencies with him. No new inspection was performed.
FIR07-00697 INSP-Sprinkler Rough-in/Hydro5/8/20085/9/20085/9/2008 12:09:31 PMAFAIL
The above ground hydro test failed.
FIR08-00120 INSP-Final Inspection5/8/20085/9/20085/9/2008 10:27:24 AMAPASS
Permit finaled