Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00717 INSP-Final Inspection5/9/20145/9/20145/9/2014 3:24:38 PMPFAIL
Not ready for a final inspection. This was a rough-in inspection. See the city approve plans for locations marked "ok" where piping can be covered.
FIR13-00639 INSP-Final Inspection5/8/20145/9/20145/9/2014 3:06:27 PMAPART
All corrections have been completed and the forward flush passed. Can not final this permit until possible modifications have been performed due to equipment being installed.
BLD13-02271 FIRE-Final Inspection5/8/20145/9/20145/9/2014 3:05:22 PMAPART
A temporary occupancy for life safety is being given until the interior equipmetent has been installed and possible fire sprinkler modifications performed.
FIR14-00240 INSP-Sprinkler Rough-in5/8/20145/9/20145/9/2014 9:15:58 AMPCANC
partial rough in Phone #: ###-#### >> Inspection requested via web by John Venche Inspection cancelled from web by: John Venche
FIR14-00240 INSP-Sprinkler Rough-in5/8/20145/9/20145/8/2014 6:54:08 PMACANC
Partial Rough in Phone #: ###-#### >> Inspection requested via web by John Venche Inspection cancelled from web by: John Venche