Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01369 Electrical Rough-In5/8/20175/9/20175/9/2017 2:09:59 PMPPASS
Call for level 1 stack 4 TI space inspection at Simplot Headquarters and sign off. Phone #: ###-#### Inspection requested via web by Tom Betty
TCO for vanilla space OK
ELE17-00975 Final5/9/20175/9/20175/9/2017 1:43:12 PMPNH
Phone #: ###-#### Inspection requested via web by Spencer McLean
No answer at door. called, will reschedule
ELE17-00536 Electrical Rough-In5/8/20175/9/20175/9/2017 1:16:22 PMPPASS
Rough in inspection on interior walls before sheet rock. Phone #: ###-#### Inspection requested via web by Kelly Tarter
J-boxes above soffit on interior drive thru side access will be provided. Discussed derating conductors with 9 or more current carrying conductors in a raceway.
Walls and hardlids rough in ok cover
ELE17-00601 Final5/9/20175/9/20175/9/2017 12:41:27 PMPPASS
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk
Final ok
ELE13-01329 DOC - Permit Expired5/9/20175/9/20175/9/2017 11:27:25 AMPPASS
Permit expired due to no response on several attempts to gain access to final
ELE17-01253 Electrical Rough-In5/8/20175/9/20175/9/2017 10:18:48 AMAPASS
Shane is the contact his cell no is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
Kitchen area not being changed and is not in scope of work however suggested GFCI protection for 120 volt receptacle outlets in kitchen. Bar wall not built. 2 small wall areas rough in ok cover
ELE17-01346 Electrical Rough-In5/8/20175/9/20175/9/2017 9:42:21 AMAFAIL
This is a re-inspect of ceiling for cover. The project manager will insulate up to the knob and tube from the east wall of the house. This will insulate the vulnerable area of the attic. Please call 30 min or more of your eta and we will get a guy right over to open the occupied home. Phone #: ###-#### Inspection requested via web by David Nelson
394.19- Knob and tube wiring shall have a clear area around wire of minimum of 3" for heat dissapation. Some insulation is too close and some hanging from wires.
ELE17-00701 Electrical Rough-In5/8/20175/9/20175/9/2017 8:44:04 AMAPASS
Grid inspection Phone #: ###-#### Inspection requested via web by Dean Gernaat Grid rough in ok cover