MEC18-01875
| Rough-in | 5/8/2018 | 5/9/2018 | 5/9/2018 4:04:22 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- Rough in not ready need to finish crawl space- need to see a 5lb flue test, gauge was at zero
|
MEC18-01875
| Pressure Test | 5/8/2018 | 5/9/2018 | 5/9/2018 4:02:05 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20 lb gas pressure test ok
|
MEC18-01670
| Final | 5/9/2018 | 5/9/2018 | 5/9/2018 3:49:53 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Chris Field- final for open burner ok
|
MEC17-03794
| Final | 5/4/2018 | 5/9/2018 | 5/9/2018 3:47:47 PM | P | PASS |
|
|
inspection after 3pm homeowner is Lacey ###-####
|
MEC17-05502
| Final | 5/9/2018 | 5/9/2018 | 5/9/2018 2:39:53 PM | P | PASS |
|
|
Inspection requested via web by Margie Rowe - furnace ac coil co ok
|
MEC18-01868
| Rough-in | 5/8/2018 | 5/9/2018 | 5/9/2018 2:17:54 PM | P | PASS |
|
|
Please do a rough-in and pressure test. Lock box code is 5234 if no one is there. Call James at ###-#### with any questions, thanks. Inspection requested via web by 4 Seasons - will need to see make up air for range vent at final- 20 lb gas test ok- fireplace R/I ok- range vent ok
|
MEC18-02065
| Pressure Test | 5/9/2018 | 5/9/2018 | 5/9/2018 1:55:02 PM | P | PASS |
|
|
Call Greg with any questions please Phone #: ###-#### Inspection requested via web by Greg Mendiola- 60 lb gas pressure test to pool heater ok
|
MEC18-01947
| Pressure Test | 5/8/2018 | 5/9/2018 | 5/9/2018 11:29:41 AM | A | CANC |
|
|
Thank you for making and acceptation and getting this taken care of at last minutue. Phone #: ###-#### Inspection requested via web by Sabrina DeHority
|
MEC18-01373
| Rough-in | 5/8/2018 | 5/9/2018 | 5/9/2018 11:03:34 AM | A | PASS |
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- R/I ok- 5lb flue pressure test on front two units ok
|
MEC18-01954
| Rough-in | 5/8/2018 | 5/9/2018 | 5/9/2018 10:16:29 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Dianne Maxwell- need approved and stamped Man J onsite- Exhaust fans need to be finished and rough in completely- missing exhaust fan in upstairs bathroom- dryer vent need to maintain 4" size. the pipe at the top plate is being smashed
|
MEC18-01954
| Pressure Test | 5/8/2018 | 5/9/2018 | 5/9/2018 10:13:54 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dianne Maxwell- 20lb gas pressure test ok
|
MEC18-00700
| Final | 5/8/2018 | 5/9/2018 | 5/9/2018 10:11:21 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ashley Stegemann- final ok
|
MEC18-01956
| Final | 5/8/2018 | 5/9/2018 | 5/9/2018 9:19:16 AM | A | NH |
|
|
Debbie Widmier is Homeowner and has plumbing inspection scheduled for 5/9 am.
Kelly Martin - Easy Heating - ###-#### Phone #: ###-#### Inspection requested via web by kelly Martin- left notice on front door
|
MEC18-02035
| Rough-in | 5/8/2018 | 5/9/2018 | 5/9/2018 9:07:08 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ashley Stegemann- fireplace R/I ok
|
MEC18-00989
| Final | 5/8/2018 | 5/9/2018 | 5/9/2018 8:36:57 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ashley Stegemann- fireplace final ok
|