Inspections for the day of: Thursday, May 9, 2019.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-04507 Final5/9/20195/9/20195/9/2019 3:47:12 PMPPASS
PLEASE CALL ONE HOUR BEFORE SO WE CAN MEET YOU ON-SITE:
###-#### Phone #: ###-#### Inspection requested via web by Rob Maes Final ok
ELE19-00533 Electrical Rough-In5/8/20195/9/20195/9/2019 3:29:20 PMPFAIL
For two bedrooms and a bathroom in the basement. Phone #: ###-#### Inspection requested via web by Steven Burch
210.52(A)- several misc locations to install receptacles to comply.
* several locations where old wiring left for temp lights and new wiring not terminated all needs terminated and old removed.
*Base board heaters wiring not complete.
*Junctions to all be accessible. few found recessed above framing.
ELE19-00948 Final5/8/20195/9/20195/9/2019 2:24:12 PMPPASS
Von is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Final ok
ELE19-01577 Conference5/8/20195/9/20195/9/2019 1:42:47 PMPDONE
Call Tony ###-#### on your way please. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
Discussed required kitchen counter top receptacles for 9' of counter top with operable windows for pass through to pool area. By definition wall space is space measured along fixed walls or panels. If windows are all operable area to be treated as penisula with receptacle at connecting edge. No additional receptacles needed for this space if all windows open.
Also area along stair rail if this would count for wall space. This area will require receptacles so no point measured along rail to be more than 6' from a receptacle outlet as per 210.52(A).
Asked why existing pool area being redone and service fees not part of permit and they explained not part of scope of work yet. Will need added and inspections shall be done for these areas as well.
ELE18-01608 Conference5/9/20195/9/20195/9/2019 12:23:24 PMPDONE
Discussed work clearance for exterior pool equipment. Fence is planned to be installe limitting access to serviceable equipment for pools. All serviceable equipment shall have minimum work clearances as per 110.26 3' depth and 30" wide for 120/208 volt.
ELE19-00430 Electrical Rough-In5/8/20195/9/20195/9/2019 12:19:34 PMAPASS
inspection for wall/ceiling cover Phone #: ###-#### Inspection requested via web by Mike McCarrel
Area noted walls and ceiling rough in ok cover
ELE18-04555 Final5/8/20195/9/20195/9/2019 12:18:11 PMAPASS
Phone #: ###-#### Inspection requested via web by Mike McCarrel Final ok
ELE18-04554 Final5/8/20195/9/20195/9/2019 12:17:43 PMAPASS
Phone #: ###-#### Inspection requested via web by Mike McCarrel Final ok
ELE19-01705 Permanent Service5/8/20195/9/20195/9/2019 11:18:41 AMAPASS
Joe Phone #: ###-####
250.53- Metal underground water grounding electrode system pipe shall have supplemental grounding electrode added. Adding ground rods. Will check on final. p/s o/h rec ok
ELE19-01700 Electrical Rough-In5/8/20195/9/20195/9/2019 11:05:55 AMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson
Job foam sealed prior to inspection. Called and informed last chance, NO COVER OF ANY KIND PERMITTED UNTIL APPROVED.
Furnace in attic, attic elec boxes trimmed at RI.
Rough in ok cover
ELE19-01700 Permanent Service5/9/20195/9/20195/9/2019 10:54:23 AMPPASS
Phone #: ###-#### Inspection requested via web by David Nelson p/s u/g n ok
ELE19-00761 Final5/8/20195/9/20195/9/2019 10:31:39 AMAPASS
Phone #: ###-#### Inspection requested via web by Kevin Burke Final ok
ELE19-00662 Final5/8/20195/9/20195/9/2019 9:26:42 AMAPASS
access: 4141 Phone #: ###-#### Inspection requested via web by David Nelson Final ok
ELE19-01637 Electrical Rough-In5/6/20195/9/20195/9/2019 8:54:51 AMAFAIL
Phone #: ###-#### Inspection requested via web by Icon Electric
* Permit discription and fee oayed is for service only, add single family dwelling and pay additional fee and recall.
* Empty light box in hall by jack and jill bath.
314.25- Recessed can junction box covers shall be completely installed to totally enclose box opening. 2 in kitchen.